Specifications
Table 1 General Specifications
INVERTER MODEL
SPF 3000TL LVM
Safety Certification
CE
Operating Temperature Range
0°C ~ 55°C
Storage temperature
-15°C ~ 60°C
Humidity
5% to 95% Relative Humidity (Non-condensing)
Dimension, mm
455 x 350 x 130
Net Weight, kg
11.5
Altitude
<2000m
Table 2 Line Mode Specifications
INVERTER MODEL
SPF 3000TL LVM
Input Voltage Waveform
Sinusoidal (utility or generator)
Nominal Input Voltage
120Vac
Low Loss Voltage
95Vac±5V (UPS); 65Vac±5V (Appliances)
Low Loss Return Voltage
100Vac±5V (UPS); 70Vac±5V (Appliances)
High Loss Voltage
140Vac±5V
High Loss Return Voltage
135Vac±5V
Max AC Input Voltage
150Vac
Nominal Input Frequency
50Hz / 60Hz (Auto detection)
Low Loss Frequency
40±1Hz
Low Loss Return Frequency
42±1Hz
High Loss Frequency
65±1Hz
High Loss Return Frequency
63±1Hz
Output Short Circuit Protection
Circuit Breaker
Efficiency (Line Mode)
>95% ( Rated R load, battery full charged )
Transfer Time
10ms typical, 20ms Max@ Single
<30ms @ Parallel
Output power derating:
When AC input voltage drops to 95V, the
output power will be derated.
Output Power
Rated Power
20% Power
65
65V 95V
140V
Input Voltage