22
10 56fault
56fault means battery connection is open
Testing method:
a. Test the real battery voltage via multimeter
b. if battery voltage is normal:
1) please confirm the battery type, for lithium-ion battery , please check 2nd and 5th option on
inverter. Too large charging current on 2nd option will cause BMS protection on battery so that it
will shut down the mosfet inside the battery, then battery connection is open. For lithium-ion
battery ,ONLY US2 or Li can be used. If lead acid battery, in usual, charging current is 0.2-0.3C
( C means battery capacity ).
2) After testing above, if 56fault still occurs. You can doubt if fuse on mainboard is broken. Please
uncover the inverter and take out MPPT board, then confirm if fuse is ok.
c. if battery voltage is abnormal, please check battery further.
Solution:
Restart the battery and inverter
OR