SPF 3500-5000 ES SPF 5000TL HVM WPV Fault condition and
Troubleshooting
Part I. Fault
1 03fault
03fault means battery voltage is too high.
Testing method:
a. Firstly ,disconnect battery from inverter and test the battery voltage separately
b. If battery voltage is normal, then connect battery into inverter and check battery voltage on LCD. Try
to adjust to the battery on LCD via inverter battery voltage setting.
Method:
1. Only connect battery to inverter( Don
’t connect to utility, PV system and load )
2. Press UP and Down at the same time for 3 seconds and type 111 , then press Enter.
3. Select battery page , S means reduce the voltage, A means increase the voltage.
4. For example, LCD displays 53V and multimeter displays 50V, then type 3V on S state. And press Enter
to save it.
5. If above all still can
’t solve the issue, it may be hardware issue. Try to replace mainboard.
Solution:
If real battery voltage is normal, while, battery voltage on LCD abnormal, you should doubt if battery
sample circuit has some trouble. Suggest replacing mainboard.
M alfunction Reason:
Battery voltage sample circuit on mainboard may have some trouble. You can try to uncover the inverter
and check inside.