background image

53

54

12 Product specification 

12.1 Growatt SPH series energy storage machine product 

specification

Model

Specifications

SPH 4000
Tl3 BH

SPH 5000
Tl3 BH

SPH 6000
Tl3 BH

SPH 7000
Tl3 BH

SPH 8000
Tl3 BH

SPH 10000
Tl3 BH

Input data(DC)

Max. recommended PV 

power(for module STC)

Max. DC voltage

Start voltage
Nominal voltage

MPP voltage range
No. of MPP trackers

No. of PV strings per 

MPP trackers

Max. input current per 

MPP 

Max. short-circuit 

current per MPP 

trackers

Output data(AC)

AC nominal power

Max. AC apparent 

power
Nominal AC 

voltage/range
AC grid 

frequency/range

Max. output current

Power 

factor(@nominal 

power)
Adjustable power factor
THDi

AC grid connection type

Stand alone(AC power)

AC nominal output 

power

Max. AC apparent power

Nominal AC voltage

Nominal AC frequency

Max. output current

5200W

7800W

10400W

6500W

9100W

13000W

1000V

1000V

1000V

1000V

1000V

1000V

160V

160V

160V

160V

160V

160V

600V

600V

600V

600V

600V

600V

160~1000V 160~1000V 160~1000V 160~1000V 160~1000V 160~1000V

2

2

2

2

2

2

1

1

1

1

1

1

1

12A/12A

12A/12A

12A/12A

12A/12A

12A/12A

12A/12A

15A/15A

15A/15A

15A/15A

15A/15A

15A/15A

15A/15A

4000W

6000W

8000W

5000W

7000W

10000W

4000VA

5000VA

6000VA

7000VA

8000VA

10000VA

230V/400V; 310~476V

50/60Hz; 45~55Hz/55~65 Hz

6.1A

7.6A

9.1A

10.6A

12.1A

15.2A

0.8leading ~ 0.8laging

<3%

3W+N+PE

4000W

5000W

6000W

6000W

6000W

6000W

4000VA

5000VA

6000VA

6000VA

6000VA

6000VA

230V/400V

50/60Hz

6.1A

7.6A

9.1A

9.1A

9.1A

9.1A

THDV

Switch time

Battery data

DC

Battery voltage range

Max. charging / 

discharging current

Continuous charging 

/ discharging power

Type of battery

Capacity of battery

Efficiency

Max. efficiency

Euro-eta

MAX. Battery 

charge/discharge 

efficiency

Protection devices

DC reverse-polarity 

protection
Battery reverse 

protection

DC switch

DC Surge protection

Insulation resistance 

monitoring

AC surge protection

AC short-circuit 

protection

Ground fault monitoring

Grid monitoring

Anti-islanding 

protection

Residual-current 

monitoring unit

General data

Dimensions (W / H / D) 
Weight

Operating temperature 

range

< 3%

< 0.5S

160~550V

21A

4000W

5000W

6000W

7000W

8000W

10000W

lithium battery / Lead-acid battery

5~50kWh

97.6%

97.8%

98.0%

98.2%

98.2%

98.2%

97.0%

97.2%

97.3%

97.4%

97.4%

97.5%

97.4%

97.4%

97.4%

97.4%

97.4%

97.4%

yes

yes

Type 

yes

Type 

yes

yes

yes

yes

yes

505*453*198mm

28kg

25 °C ~ +60 °C(–13 °F ~ +140 °F)

With derating above 45 °C(113 °F)

yes

Summary of Contents for SPH 10000TL3 BH

Page 1: ...an Street Bao an District Shenzhen P R China No 28 Guangming Road Shiyan Street Bao an District Shenzhen P R China GR UM 158 A 00 GR UM 158 A 00 86 0755 2747 1942 86 0755 2747 1942 www ginverter com w...

Page 2: ...ty Measure 2 3 Symbols introduction on the SPH inverter Purpose Use 1 1 Preface 1 2 Target Group 1 3 Product Description 1 4 Safety Instructions 3 Product Description 4 Unpacking 5 Installation 5 1 5...

Page 3: ...ter 14 1 storage machine product specification 14 2 DC input terminal parameter 14 3 Torque 14 4 Appendix Growatt SPH series energy 11 Decommissioning 6 Commissioning 12 Product specification 7 1 Star...

Page 4: ...Installer can install energy storage machine of Growatt SPH TL3 BH Series rapidly and troubleshooting build communication system through read this manual carefully If you have any questions in the pro...

Page 5: ...tilation of the service environment and temperature control in order to prevent the danger of battery explosion Battery recommended installation environment must be strictly in accordance with the spe...

Page 6: ...ating 3 2 Label Explanation Label contains the following information for example SPH 10000TL3 BH shows as below Caution risk of danger Danger to life due to high voltage in SPH There is residual volta...

Page 7: ...ers Safety level Ingress Protection Operation Ambient Temperature Certificates Number Growatt SPH 10000TL3 BH 1000Vdc 160 1000Vdc 15A 2 12A 2 10000W 10000VA 3W N PE 230 400Vac 15 2A 50Hz 60Hz 0 8 lead...

Page 8: ...setscrew Ground terminal M4 setscrew Mc4 connector black connector Installation 5 5 1 Basic installation requirements A The installation location must be suitable for SPH s weight for a long period ti...

Page 9: ...space into account about the dimensions please reference user manual N The Inflammable and explosive dangerous goods must not be placed around battery in case of cause serious danger 5 2 Installation...

Page 10: ...board installation guide put the cardboard on the wall and make sure the top edge of the cardboard is horizontal 3 Mark four points at the wall via the hole of the paper board then remove the cardboar...

Page 11: ...not connect to DC source 5 4 2 Connection of AC terminal and off grid terminal SPH has a grid output terminal and off grid out terminal look down on the SPH from the front the terminal on the left on...

Page 12: ...inal and EPS output terminal connection steps as follow Step 1 Uninstall the AC terminal as below chart Step 2 Thread cables through pressure screw seal ring threaded sleeve in sequence insert cables...

Page 13: ...d storage system Notice If you want to use on gird only please refer to chart 5 17 Connect with AC grid and float EPS OUTPUT If you have no battery now you can also float BAT terminal and this hybrid...

Page 14: ...must be larger than 12AWG 5 4 4 Connection of meter terminal When customer needs to use meter to monitor the energy flow the meter terminal connection steps are as follows Step1 Reference 5 2 make LAN...

Page 15: ...the filler plug from the cable support sleeve Step5 Route the CAN cable through an opening in the cable support sleeve Step6 Thread the CAN cable through the cable gland Step7 Insert the RJ45 plug of...

Page 16: ...d lock the waterproof cover to the inverter with screws Step9 Screw the swivel nut onto the waterproof cover 5 4 7 Connection of DRMS terminal Australia only When SPH is applied to Australia the DRMS...

Page 17: ...on the inverter until it snaps into place Step8 If no other cables need to be installed lock the waterproof cover to the inverter with screws Step9 Screw the swivel nut onto the waterproof cover PIN...

Page 18: ...the cable such as Dry contact cable is not used please do not remove the filler plug from the cable support sleeve 5 4 10 Grounding connection SPH must be grounded by cable the grounding point is show...

Page 19: ...rge battery by PV power as large as it can do If the customer enables the AC CHG AC grid charging functions Inverter will charge battery by PV power and AC power from grid as large as it can do Grid f...

Page 20: ...d Each small white PIN has two statuses when set upward to ON its value turns to 1 when set downward its value turns to 0 Concerning the matching of the PIN status and the country safety standard plea...

Page 21: ...XXXXB GT0XXXXXXC GT0XXXXXXD GT0XXXXXXE GT0XXXXXXF GT1XXXXXX0 6 5 4 3 2 1 ON DIP 6 5 4 3 2 1 ON DIP 6 5 4 3 2 1 ON DIP 6 5 4 3 2 1 ON DIP TAIWAN EN50549 Ireland India Brazil GT1XXXXXX2 GT1XXXXXX3 GT1XX...

Page 22: ...Fault Location Description A B D C E Status ESC button cancel control Down button Enter button UP button Notice LED showing status of SPH it has two colors one is green and another is red Please turn...

Page 23: ...Mode Ppv xxxx xxxxW PV1 PV2 voltage Battery information WorkMode Grid_R xxxV xxHz WorkMode EPS_R xxxV xxHz WorkMode Po xx xkW GridS information Output AC Power EPS R information WorkMode Pbat XXXX W B...

Page 24: ...Power Rate 100 Power Rate 100 Priority WorkMode WorkMode Opt Load First WorkMode WorkMode WorkMode AC CHG Enable WorkMode SC _ _ _ _ WorkMode 00 00 00 00 WorkMode Save OK WorkMode Time WorkMode 00 00...

Page 25: ...we can quickly update the software of machine You can see USB A as below Note USB is only used for firmware update Customer can t use it for charging 6 5 2 Use of RS232 port RS232 port is mainly used...

Page 26: ...Before use WIFI communication you should make sure the follow PIN1 and PIN2 are ON Start up and shut down SPH system 7 7 1 Start up the SPH system Users can start up SPH inverters through following st...

Page 27: ...rature output after temperature back to normal system can work normally please be patient at this time If the temperature is too low it is possible that battery will be low temperature protection at t...

Page 28: ...is lost or not 2 Check the grid connection is good or not 3 Check the switches on the cable are on or not 1 Restart inverter 2 Please contact Growatt service center if restart can t solve the problem...

Page 29: ...3 Shenzhen Growatt New Energy Technology Co Ltd confirms that the Growatt inverters and accessories described in this document are in compliance with the above mentioned EU directives The entire EU De...

Page 30: ...A 15A 15A 15A 15A 15A 15A 15A 15A 15A 15A 15A 4000W 6000W 8000W 5000W 7000W 10000W 4000VA 5000VA 6000VA 7000VA 8000VA 10000VA 230V 400V 310 476V 50 60Hz 45 55Hz 55 65 Hz 6 1A 7 6A 9 1A 10 6A 12 1A 15...

Page 31: ...system voltage IP68 0 25m model 1000V DC UL 1000V DC TUV 32A 40A 44A 65A 55 56 12 3 Torque 12 4 Appendix The following chart is the energy storage machine optional appendix list if there is a need pl...

Page 32: ...ion code 5 SPH inverter Display content 6 The manufacturer and model of the battery 7 Battery capacity and connection mode Annex AutoTest only for Italy Follow is the chart of Auto Test refer to 6 4 4...

Reviews: