19
P00.04
Upper limit of the
running frequency
P00.05~ P00.03
The paramater is the upper limit of the output
frequency of
the inverter which is lower than or
equal the maximum frequency
50.00Hz
P00.05
Lower limit of the
running frequency 0.00Hz~ P00.04
If the solar energy is not sufficient to power the
motor
,
inverter will drop frequency runing. The
inverter will stop run when the runing frequency
lower than the lower limit frequency
0Hz
P00.13
Set direction
0~2
0
:
T
he inverter runs in the forward diretion
1
:
T
he inverter runs in the reverse diretion
2
:
Forbid to run in reverse diretion
0
P00.18
Function restore
parameter
0~1
0
:
No operation
1
:
Restore the default value
0
P01.08
Stop mode
0~1
0
:
Decelerate to stop
1
:
Coast to stop
1
P02.01
Rated power of
asynchronous
motor
0.1~ 3000.0kw
Set this parameter according to rated power on
the pump nameplate
NOTE:
when resetting the rated power of the
motor(P02.01),you can initialize the motor
parameter of (P02.02~P02.05)
Model
confirmation
P02.02
Rated frequency
of asynchronous
motor
0.01Hz ~ P00.03
Set this parameter according to rated frequency on
the pump nameplate
50.00Hz
P02.04
Rated voltage of
asynchronous
motor
0 ~ 1200V
Set this parameter according to rated voltage on
the pump nameplate
Model
confirmation
P02.05
Rated current of
asynchronous
motor
0.8 ~ 6000A
Set this parameter according to rated current on
the pump nameplate
Model
confirmation
P02.27
Motor overload
protection factor
20.0%~120.0%
The pump motor over-load protection factor when
over-load, please refer to the rated current of
motor to set this parameter.
100.0%
P15.00
PV Inverter
Selection
0
:
Disable
1
:
Enabled
0
:
means the function is invalid
1
:
means the MPPT function is enabled
1
P15.04
PID Max. Output
Frequency
P15.05~100.0%
P15.05~100.0%(100%correspongs P00.03)
P15.04 is used to limit the Max. value of target
frequency
100.0%
P15.05
PID Min. Output
Frequency
0.0%~100.0%
0.0%~ P15.04(100%correspongs P00.03)
P15.04 is used to limit the Min. value of target
frequency
0.0%
P15.13
Delay Time of
Dry-Water
0~10000S
Delay Time settiing of dry-water
,
under
auto dry
run mode or water sensor mode
60S