20
P15.14
Wake-up Delay
Time
of Dry-Water
0~10000S
Dry out recovery time
,
under auto dry run mode or
water sensor mode
600S
P15.15
Automatic Dry run
protection
0.0~100.0%
0.0%:No automatic dry run protection
0.1%~100.0%:It is determined by P15.15
100% corresponds to the rated motor current.
If the running frequency >30Hz
,
and the current
corresponding to the current frequency is less than
P15.15,
after the time set by P15.13,
the inverter
will stop run
,
otherwise
,
it will operate normally.
After the time set by P15.14,
the inverter will
reset.
0.0%
P15.16
Delay Time of
Full-Water
0.0~1000.0S
Delay Time setting of Full-water
,
under water
sensor mode
60.0S
P15.18
Reset Delay of
Full-Water
0.0~1000.0S
Dry out recovery time
,
under water sensor mode
120.0S
P15.19
Frequency of
Weak Light
0.00~50.00Hz
If the output frequency is less than the frequency
of Weak Light
,
it will stop run.
5.00Hz
P15.20
Delay Time of
Weak Light
0.0~3600.0S
Delay Time of weak light, after the time set by
P15.20, the inverter will stop run.
100.0S
F15.21
Reset Delay of
Weak Light
0.0~3600.0S
Reset Delay of weak light,after the time set by
P15.21, the inverter will reset
300.0S
Troubleshooting
The inverter has complete protection. When a failure occurs, the inverter will take protective measures. The
general protection is to stop the motor from running and forbid it to restart within a certain period.
Fault Code
Fault type
Possible Reasons
Solution
Power off
No failure
\
\
Inc OVP
Dec OVP
Const OVP
Overvoltage
1.
Input voltage is too high
2.
There is large energy feedback
1.Check the voltage of solar
array
2.Check if the DEC time of the
load is too short or the inverter
starts during the rotation of the
motor
Bus low
Undervoltage
1.Input voltage is too low;
2.Illumination intensity is too weak
Check the voltage of solar array