background image

1

.

2

.

SYN 50-XH-1

 Quick Guide

Overview

Installation

System overview

2.1

 Installation requirements

2.2

 Installation steps

1

Front panel

2

LED indicator

3

Screw for top cover

4

The main frame body

5

Mounting bracket

6

COM wiring port

7

Generator wiring port

8

Grid wiring port

9

Inverter wiring port

10

Load wiring port

11

Waterproof plugs

No.

Name

Size

No.

Name

Size

1

straight 

screwdriver

Φ

5mm

2

hammer

/

3

Allen wrench

Φ

5mm

4

Cross rise

Φ

5mm

5

Electric drill 

Φ

6mm

6

Wire stripper

/

7

Line pressing 

pliers

/

2

.

3

 

Required tools

3

.

2

 

 Wiring instructions

1.Take out the two screws on the upper cover of the machine, open the upper cover, and do not 
remove the ugly plate inside the machine.
2.Loosen the plastic cover printed as " Grid " counterclockwise, remove the three waterproof plugs, 
and reserve three holes.
3.Route the three power grid cables (L/N/PE) through the three holes and connect them to the power 
grid input terminal and the ground copper bar. The screw torque on the power grid terminal is 26.5 
in*lbs / 3.0 N*m to 31 in*lbs / 3.5 N*m, and the screw torque on the ground terminal is 13 in*lbs / 1.5 
N*m.
4.Finally, fasten the plastic cover clockwise. Wiring is shown as follows:

Grid

DC

AC

PV

AC

AC

AC

DC

Generator

Battery

Inverter

Load

The front, back and side pictures of the machine are as follows:

1.Determine 

SYN 50-XH-1

 mounting location, on a wall, stud framing or pole. It is recommended to mount the Backup Interface in a location 

protected from direct sunlight.
2.To allow proper heat dissipation, maintain at least a 300mm clearance between the SYN 50-XH-1 and other objects.
3.Position the mounting bracket against the wall/pole and mark the drilling hole locations.
4.Drill the holes and mount the bracket. Verify that the bracket is firmly attached to the mounting surface.
5. Hang SYN 50-XH-1 on the bracket.

 

1

2

3

4

5

6

300mm

300mm

300mm

300mm

500mm

3

.

Wire specification suggestions

The cable specifications of this machine are as follows, and the wiring end is stripped 10mm.

project

Wire diameter

Line length

Grid input cable

6-8AWG

10m

Inverter input cable

8-12AWG

20m

Load output cable

8-12AWG

20m

Generator input cable

6-8AWG

10m

Communication cable

22-26AWG

20m

6-8AWG

10m

L

10mm

10m

6-8AWG

6-8AWG

N

10mm

10m

PE

10mm

Grid and Generator AC cable

20m

10-12AWG

L

10mm

20m

10-12AWG

10-12AWG

N

10mm

20m

PE

10mm

Load and lnverter AC cable

20m

20m

24-26AWG

24-26AWG

L

10mm

N

10mm

Communication cable

3

.

2

.

1 Connecting SYN 50-XH-1 to the Grid

3

.

2

.

2  Connecting SYN 50-XH-1 to the Inverter

When connecting theSYN 50-XH-1 to the XH Inverter, we need to connect AC power cable and communication cable.

1.Loosen the plastic cover printed as "Inverter" counterclockwise, remove the three waterproof plugs, and reserve three holes.
2.Route the cables of the three inverters (L/N/PE) through the three holes, connect the cables to the inverter circuit breaker terminal and the 
ground copper bar. The screw torque of the inverter circuit breaker terminal is 17.5 in*lbs / 2 N*m, and the screw torque on the ground 
terminal is 13 in*lbs / 1.5 N*m.
3.Finally, fasten the plastic cover clockwise. Wiring is shown as follows:

2

1

3

5

4

6

7

8

9

10

11

11

15°

≥300mm

365

9

2

.5

4

9

0

.3

134.7

120.2

7

Grid

Grid

L N

PE L

PE

N

Connection to the Grid

PE

1

2

1)To connect to the AC cable:

1

3

Reviews: