OPERATION GUIDE
These SETTINGS will ensure proper operation.
Operating
Modes
DAY
HUMIDITY
NIGHT
HUMIDITY
DAY
TEMPERA-
TURE
NIGHT
TEMPERA-
TURE
LOW
TEMP
LIMIT
(NOTE 2)
COOL
Setting not
used
Setting not
used
Day Setpoint:
52°F to 100°F
(right scale)
Night Setpoint:
52°F to 100°F
(right scale)
Setting not
used
DEHUMIDIFY
Day Setpoint:
15% to 95%
(left scale)
Night Setpoint:
15% to 95%
(left scale)
Set value to 50°F
or above
(Note 2)
Set value to 50°F
or above
(Note 2)
Set value to
48°F or
above
(Note 2)
COOL &
DEHUMIDIFY
Day Setpoint:
15% to 95%
(left scale)
Night Setpoint:
15% to 95%
(left scale)
Day Setpoint:
52°F to 100°F
(right scale)
Night Setpoint:
52°F to 100°F
(right scale)
Set value to
48°F or
above.
HUMIDIFY
Day Setpoint:
15% to 95%
(left scale)
Night Setpoint:
15% to 95%
(left scale)
Setting not used Setting not used Setting not
used
HEAT
Setting not
used
Setting not
used
Day Setpoint:
52°F to 100°F
(right scale)
Night Setpoint:
52°F to 100°F
(right scale
Setting not
used
SETTINGS FOR EACH CONTROL MODE:
Note 2: The Low Temperature Limit will stop your dehumidifying equipment if the
temperature in the room cools down below this setting to avoid damaging your plants.
This limit is active ONLY when “DEHUMIDIFY” or “COOL & DEHUMIDIFY” CON-
TROL MODE is selected. Always set your DAY and NIGHT temperature settings NOT
MORE THAN 2°F above the Low Temp Limit.
4