1.2 Sanitary
Installation
When installing the GENO
®
-flushing compressor 1988 K certain rules
must always be followed. Additional recommendations facilitate work
with the GENO
®
-flushing compressor 1988 K.
Binding
rules
The installation of a flushing compressor represents a major intervention
in the drinking water installation and thus must only be performed by an
approved installation company.
Observe the local installation guidelines and the general regulations.
Warning!
Risk of infection due to germ-infested water. In stagnant
water germs can multiply beyond safe limits. Ensure good hygiene when
working on and with the flushing compressor. Always drain off any
remaining water / disinfect parts which have come into contact with
water.
Note:
Prerequisites for flushing, disinfection and commissioning of a
drinking water installation:
a house connection for the water supply which has been flushed
through by a water company and approved for use,
availability of water as per the German water drinking ordinance
(TrinkwV),
that pressure and leakage tests have been performed on the drinking
water installation as per DIN EN 806-4 6.1 and that the results were
documented
that a filter as per DIN EN 13443-1 is fitted on the house connection.