6.4.1 Installation Diagram of
Oxiperm 164 Chlorine
Dioxide System with Solenoid
Valve
Oxiperm 164 with solenoid valve
The Oxiperm
®
C 164 is delivered as standard with a solenoid valve in the dilution
water line.
This version is designed for systems where the supply of dilution water and the
addition of chlorine dioxide solution are not to be carried out in the same water
circuit.
A requirement for correct functioning of the system is a water pressure of at least
1 bar up to maximum 10 bar.
In addition, the back-pressure at the connection of the solution line on the Oxiperm
®
C 164 should be at least 0.5 bar less than the inlet pressure of the dilution water.
Caution
With the chlorine dioxide solution line shut off (at the
outlet) and an input pressure of more than 10 bar in the
dilution water line (at the inlet), there is a danger that
the system will be damaged. The solution line must
therefore be provided with an excess pressure valve
set to 10 bar.