English (GB)
8
3.1 Connecting the LON
Grundfos recommends to use a cable according to
Echelon standards.
Examples of recommended cable types
•
Belden 85102
•
Belden 8471
•
Level IV, 22 AWG
•
JY(St) Y 2 x 2 x 0.8
•
TIA Category 5.
A LON network must be terminated. The termination
depends on the network topology chosen.
Fitting the cable
Procedure:
1. Connect the conductors to terminal A (pos. 1).
2. Connect the conductors to terminal B (pos. 2).
3. Connect the twisted screen ends to terminal
"Screen" (pos. 3).
Fig. 2
Connecting the LON
3.2 Registration in a LON network
Grundfos products with a CIM 1XX LON module are
registered by a LON network in one of these ways:
•
Service pin
•
Bar code label.
Service pin
When the service pin push-button of the module
is activated, the module will send a unique 48 bit
ID code (Neuron ID) which is registered in the
LON network.
Fig. 3
Service pin
Bar code label
The Neuron ID on the module or on the enclosed bar
code label is scanned and registered in the LON
network. The bar code of the Neuron ID is in Code
128 format. The additional bar code label can be
attached to the building installation plan.
4. LEDs
The CIM 1XX LON module has two LEDs. See fig. 1.
•
Yellow service LED (LED1)
•
Red/green status LED (LED2) for internal
communication between the CIM 1XX and
the Grundfos product.
LED1
The yellow LED on the CIM 1XX functions as a
service LED. When the Grundfos product is
connected to the power supply, the service LED will
flash once and then remain off if the installation has
been made correctly. In case of deviations, see
section 5. Fault finding.
LED2
Note
The screen must only be connected to
the screen terminal of the CIM 1XX LON
module. See fig. 2, pos. 3.
The cable screen must never be
connected to earth via the earth clamp.
See fig. 2, pos. 4.
Note
The stripped part of the cable screen
must be as short as possible to reduce
the impedance at high frequencies.
TM
04
19
57
15
08
Pos.
Description
1
LON terminal A
2
LON terminal B
3
LON terminal for cable screen
4
Earth clamp
2
3
1
4
TM
04
1
958
15
08
Status
Description
Off
The CIM 1XX has been switched
off.
Flashing red
No internal communication
between the CIM 1XX and
the Grundfos product.
Permanently
red
The CIM 1XX does not support
the Grundfos product connected.
Permanently
green
Internal communication between
the CIM 1XX and the Grundfos
product is OK.