9
5.3 CIM status register block
Registers in this block can be read by means of function codes 0x03 and/or 0x04. They are read-only. This block can be used for various
kinds of fault finding.
Address
Register name
Description
00021
GENIbusCRCErrorCnt
Holds a CRC error counter for the connection between the CIU 250 and the MP 204.
00022
GENIbusDataErrorCnt
Holds a data error counter for the connection between the CIU 250 and the MP 204.
00023
VersionNumber
A Grundfos-specific version number. This is an unsigned integer value.
00024
ActualModbusAddress
Holds the current Modbus slave address of the device.
Valid value range: 1…247.
00025
00026
GENIbusTXcountHI
GENIbusTXcountLO
Holds a transmit counter for total number of telegrams sent from the CIU 250 to the
MP 204.
00027
00028
GENIbusRXcountHI
GENIbusRXcountLO
Holds a receive counter for total number of telegrams received by the CIU 250 from the
MP 204.
00029
GeneralStatus
Bit 0: ScadaPinCodeEnabled
PIN code functionality.
0 = No PIN code required
1 = PIN code required to perform remote control and configuration.
Activation of SCADA PIN code protection takes place via the SMS command
SCADACODE. See "CIM 25X SMS commands" (supplement to installation and operating
instructions) on the CD-ROM supplied with the GSM module.
GeneralStatus
Bit 1: WriteAccess
Remote write access.
0 = No write access (the PIN code is incorrect).
1 = Full write access (the PIN code is either correct or not enabled).
00030
UnitFamily
Grundfos product family.
00031
UnitType
Grundfos product type.
00032
UnitVersion
Grundfos product version.