24|
P a g e
To achieve best level of protection of the pump, it is essential that parameter
calibration be done immediately after successful pump installation or pump
maintenance.
PARAMETER CALIBRATION:
Pump/s must be able to pump water to enable correct calibration. If pumps
are calibrated without water, overload and pump stalled errors may occur
1.
Press the
MODE
key to switch to manual
mode. If the controller is locked press
MODE and STORE keys together and hold
until the countdown timer stops and mode
switched from Auto to Manual Make sure
that the pump is not running and LCD
screen is displaying:
2.
Press the
A START
key to run pump A,
confirm the pump and all pipe
network is in normal working state
(including voltage, amps etc.) with
LCD screen displaying:
3.
Press and hold the
START
key and release
when the countdown starts. The controller
makes a “beep” and a countdown starts
with the LCD displaying: Controller now
counts down from 8 seconds:
5. Pump A is ready for running.
4. The pump stops running and
parameter calibration is completed
with LCD displaying:
6. Press the
B START
key to repeat
calibration for pump B. And follows
the same procedure.
OPERATION
BEFORE YOU START -
Parameter calibration and erasing