The CIM module is unable to communicate with the product.

Cause

The CIM module is installed incorrectly.

Remedy

Ensure that the module, including cables, is fitted correctly.

Cause

The CIM module is defective.

Remedy

Contact Grundfos.

Related information

2.2.5 Installing a communication interface module

8.21 Code 163 (Motor-drive protection function

measurement fault)

Alarm code 163 is shown on the display.

The alarm symbol on the display turns red, but the pump's
operating mode is unchanged.

Alarm code 

Motor drive protection function measurement

fault

 is displayed in Grundfos GO Remote.

Grundfos GO
Remote menu

Input

Output

3 Phase

3 phases without
neutral (L3
connected to N)

3-phase pumps connected
to T1-T2-T3.

3 Phase with
neutral

3 phases with
neutral

3-phase pumps connected
to T1-T2-T3.

2 phase L1-L2-N

2 phases with
neutral

2-phase pumps: P1
connected to T1-N. P2
connected to T2-N.

1 Phase L1-N

1 phase with
neutral

1-phase pumps: P1
connected to T1-N. P2
connected to T1-N.

Cause

The measured current is above the limit.

Remedy

Make sure that the 

Mains Power connection

 setting in

Grundfos GO Remote is configured correctly according to
input connections.

Make sure that the 

Mains Power connection

 setting in

Grundfos GO Remote is configured correctly according to
pump connections.

Make sure that the pump is connected to the correct
contactor terminals (T1, T2, T3) depending on the
configuration in 

Mains Power connection

.

Remove load from non-configured contactor terminals (T2,
T3) depending on the configuration in 

Mains Power

connection

.

8.22 Code 165 (Signal fault)

Alarm code 165 is shown on the display.

The alarm symbol on the display turns red and the pump stops.

Alarm code 

Signal fault

 is displayed in Grundfos GO Remote.

Cause

The signal from the sensor is out of the configured range.

Remedy

Go to 

Settings

 > 

Level control

 in Grundfos GO Remote and

ensure that the configured range corresponds to the physical
application type.

Change the sensor, if needed.

Related information

6.6.1 Setting the after-run delay, high level

8.23 Code 181 (Signal fault, PTC input)

Alarm code 181 is shown on the display.

The alarm symbol on the display turns red and the pump stops.

Alarm code 

Signal fault, PTC input

 is displayed in Grundfos

GO Remote.

Cause

There is a signal fault in the PTC input.

Remedy

Make sure that the two PTC wires from the pump are
connected correctly to the terminals on the product.

Make sure that the third PTC wire is left unconnected, if
present. 

Make sure that the PTC wires are undamaged.

Make sure that the PTC sensors within the pumps are
undamaged.

Perform a test by disconnecting the PTC wires from the
pump and shorting PTC1 terminal A and B and also PTC2
terminal A and B, and verify that the error is cleared.

Replace the product due to damaged PTC circuit. Contact
Grundfos.

Related information

2.3.3 Connecting the pump supply and power supply

8.24 Code 191 (High water level)

Alarm code 191 is shown on the display.

The alarm symbol on the display turns red, but the pump's
operating mode is unchanged.

Alarm code 

High water level

 is displayed in Grundfos GO

Remote.

Cause

The defined start level did not start the pump.

Remedy

Check and configure the sensor start level.

Cause

The pump is not big enough to remove the water.

Remedy

Contact Grundfos or an authorised service workshop. 

Cause

The level sensor is defective and not reacting on level changes.

Remedy

Check the functionality of the level sensor. 

Related information

3.6 Configuring the IO terminals using Grundfos GO Remote

8.25 Code 205 (Level switch inconsistency)

Alarm code 205 is shown on the display.

The alarm symbol on the display turns red and the pump
stops. 

Alarm code 

Level switch inconsistency

 is displayed in

Grundfos GO Remote.

Cause

A float switch could be defective or stuck.

Remedy

Check the functionality of each float switch.

Related information

3.6 Configuring the IO terminals using Grundfos GO Remote

6.6.1 Setting the after-run delay, high level

8.26 Code 220 (Contactor wear out)

Warning code 220 is shown on the display if you press
the 

Up

 or 

Down

 button.

23

English (GB)

Summary of Contents for LC 231

Page 1: ...LC 231 Dual pump unit Installation and operating instructions LC 231 dual pump unit Installation and operating instructions Other languages http net grundfos com qr i 99480674 GRUNDFOS INSTRUCTIONS...

Page 2: ......

Page 3: ...Magyar HU Telep t si s zemeltet si utas t s 243 Italiano IT Istruzioni di installazione e funzionamento 264 Lietuvi kai LT rengimo ir naudojimo instrukcija 286 Latvie u LV Uzst d anas un ekspluat cija...

Page 4: ...499 CN 522 AR 541 4 LC 231 Table of contents...

Page 5: ...e product 20 8 1 Overview of alarm and warning codes 20 8 2 Code 2 Power phase missing 20 8 3 Code 4 Too many motor restarts 21 8 4 Code 9 Power phase sequence wrong 21 8 5 Code 12 Service needed 21 8...

Page 6: ...Connecting the pump supply and power supply 2 2 2 Removing the front cover The front cover must be removed to make any connections or to install the Communication Interface Module CIM Use an antistati...

Page 7: ...nnections Use an antistatic service kit when handling electronic components This prevents static electricity from damaging the components 1 Loosen the screws and remove the front cover Be careful not...

Page 8: ...s Do not add additional components other than those illustrated on the wiring diagram Do not use unused pin holes for other connections All cable glands and plugs must be mounted after the installatio...

Page 9: ...L2 L3 L1 PE N N N L2 L3 L1 N B A B A PE PE PE PTC1 PTC2 T2 T3 T1 T2 T3 T1 M1 M2 TM070126 Three phase connections for two pumps L2 L3 L1 PE N N L2 L3 L1 B A B A PE PE PE PTC1 PTC2 T2 T3 T1 T2 T3 T1 M1...

Page 10: ...vel 1 Loosen the screws and remove the front cover Be careful not to damage the cable between the front cover and the back cover 2 Lead the wires through one of the cable glands 3 Depending on the typ...

Page 11: ...ter level 8 25 Code 205 Level switch inconsistency 3 7 Testing the product When you have made all the electrical installations and completed the startup wizard you can test the system For emptying app...

Page 12: ...ill 1 2 3 4 5 TM0713351 Designation Description 1 High level 2 Stop level 3 Start level P1 start level for pump 1 4 Start level P2 start level for pump 2 5 Dry running level In the filling application...

Page 13: ...t 5 Version number and material number 6 Production code year and week 7 Serial number 8 IC only for UL variants 9 FCC text only for UL variants 10 FCC ID only for UL variants 11 Factory code 12 IP cl...

Page 14: ...ements to avoid malfunction 6 1 Setting the application type with Grundfos GO Remote 1 Go to Settings Level control Application type 2 Select the type Empty Fill Related information 3 3 Startup wizard...

Page 15: ...artly empty the pit The after run delay should be set so that the pump stops at the normal stop level to avoid dry running In case of an error the product reports error 165 Signal fault or error 205 L...

Page 16: ...empts within a set interval 1 Go to Settings Max number of restarts 2 Enable the function 3 Set the interval within which the allowed number of restarts are to be counted 4 Set the maximum number of p...

Page 17: ...to its normal stage when the temperature has dropped to its trigger level If there is moisture in the pump then the moisture sensor will keep the series connection open until the pump is opened and se...

Page 18: ...te the warning Contactor wear out appears When 100 of the estimated wear out for the contactor is reached the alarm code 220 Contactor wear out appears on the operating panel and the controller will n...

Page 19: ...onics Network Intercommunications bus is a fieldbus developed by Grundfos to meet the need for data transfer in all typical Grundfos motor or pump applications Grundfos devices with GENIbus can be wir...

Page 20: ...itch off the power supply before you start any work on the product Make sure that the power supply cannot be switched on accidentally Fault finding and fault correction must be carried out by qualifie...

Page 21: ...Wrong configuration Alarm code 25 is shown on the display The alarm symbol on the display turns red and the pump stops Alarm code Wrong configuration is displayed in Grundfos GO Remote Cause The leve...

Page 22: ...shown on the display The alarm symbol on the display turns red and the pump stops Alarm code Drive unit communication fault is displayed in Grundfos GO Remote Cause Internal communication fault Remedy...

Page 23: ...e Change the sensor if needed Related information 6 6 1 Setting the after run delay high level 8 23 Code 181 Signal fault PTC input Alarm code 181 is shown on the display The alarm symbol on the displ...

Page 24: ...1 7 6 DOL PI 7 6 A2 and 40 C 104 F 1 When the maximum number of running pumps is set to 1 it is possible to set the nominal pump current to 12 A 2 When the maximum number of running pumps is set to 1...

Page 25: ...2 3 2 Protection of controller and supply cables 7 2 Replacing the battery 10 Disposing of the product This product or parts of it must be disposed of in an environmentally sound way 1 Use the public...

Page 26: ...ps Korea Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam ku 135 916 Seoul Korea Tel 82 2 5317 600 Fax 82 2 5633 725 Latvia SIA GRUNDFOS Pumps Latvia Deglava biznesa centrs Augusta Deglava iel 60...

Page 27: ...demarks displayed in this material including but not limited to Grundfos the Grundfos logo and be think innovate are registered trademarks owned by The Grundfos Group All rights reserved 2020 Grundfos...

Reviews: