18. Setting by means of PC Tool E-products
Special setup requirements differing from the settings available
via the GO Remote or R100 require the use of Grundfos PC Tool
E-products. This again requires the assistance of a Grundfos
service technician or engineer. Contact your local Grundfos
company for more information.
19. Priority of settings
The priority of settings depends on two factors:
1. control source
2. settings.
2. Settings
• Operating mode Stop
• Operating mode Max. (maximum curve)
• Operating mode Min. (minimum curve)
• Setpoint setting.
An E-pump can be controlled by different control sources at the
same time, and each of these sources can be set differently.
Consequently, it is necessary to set an order of priority of the
control sources and the settings.
Priority of settings without bus communication
Example:
If the E-pump has been set to operating mode Max.
(Max. frequency) via an external signal, such as digital input, the
control panel or GO Remote or R100 can only set the E-pump to
operating mode Stop.
Priority of settings with bus communication
Example:
If the E-pump is operating according to a setpoint set
via bus communication, the control panel, GO Remote or R100
can set the E-pump to operating mode Stop or Max., and the
external signal can only set the E-pump to operating mode Stop.
20. External forced-control signals
The pump has inputs for external signals for these forced-control
functions:
• Start/stop of pump
• Digital function.
20.1 Start/stop input
Functional diagram: Start/stop input
1. Control source
Control panel
GO Remote or R100
External signals
(external setpoint signal, digital inputs, etc.).
Communication from another control system via
bus
If two or more settings are activated at the same
time, the pump will operate according to the function
with the highest priority.
Priority
Control panel, GO
Remote, or R100
External signals
1
Stop
2
Max.
3
Stop
4
Max.
5
Min.
Min.
6
Setpoint setting
Setpoint setting
Priority
Control panel,
GO Remote or
R100
External
signals
Bus
communication
1
Stop
2
Max.
3
Stop
Stop
4
Max.
5
Min.
6
Setpoint setting
Start/stop (terminals 2 and 3)
Normal duty
Stop
Q
H
Q
H