5.5.2 Digital inputs
See fig. 15, pos. 2.
The digital input can be used for external control of start/stop or
forced max. or min. curve.
If no external on/off switch is connected, the jumper between
terminals Start/Stop (S/S) and frame ( ) should be maintained.
This connection is the factory setting.
Fig. 18 Digital input
External start/stop
The pump can be started or stopped via the digital input.
External forced max. or min. curve
The pump can be forced to operate on the max. or min. curve via
the digital input.
Select the function of the digital input on the pump control panel
or with Grundfos GO Remote.
TM0
5 333
9
1
21
2
Contact symbol
Function
M
A
Max. curve
100 % speed
M
I
Min. curve
25 % speed
S/S
Start/Stop
Frame connection
Start/stop
Normal duty
Note: Factory setting with
jumper between S/S and
.
Stop
S/S
M
I
M
A
On/off timer
Start/stop
S/S
Q
H
S/S
Q
H
Max. curve
Normal duty
Max. curve
Min. curve
Normal duty
Min. curve
M
A
Q
H
M
A
Q
H
M
I
Q
H
M
I
Q
H
Summary of Contents for MAGNA3 Series
Page 3: ......
Page 6: ...GRUNDFOS INSTRUCTIONS MAGNA3 Installation and operating instructions ...
Page 102: ...34 of 36 2009 D 664 07 09 Notes ...
Page 103: ...35 of 36 2009 D 664 07 09 Notes ...
Page 121: ......
Page 122: ......
Page 132: ......
Page 133: ......
Page 134: ...Coordinate power and control requirements with respective trades ...
Page 135: ......
Page 136: ......
Page 137: ......
Page 138: ......
Page 140: ......
Page 142: ......
Page 143: ......
Page 144: ......
Page 145: ......
Page 146: ......
Page 147: ......
Page 148: ......
Page 149: ......
Page 150: ......
Page 151: ......
Page 152: ......