En
gl
is
h (
G
B)
50
12. Priority of settings
You can always set the motor to operation at
maximum speed or to stop with R100 or Grundfos
GO.
If two or more functions are enabled at the same
time, the motor operates according to the function
with the highest priority.
Example
If you have set the motor to maximum speed via the
digital input, the motor control panel, R100 or
Grundfos GO can only set the motor to "Manual" or
"Stop".
The priority of the settings appears from the table
below:
*
"Stop" and "Max. speed" settings made with
R100, Grundfos GO or on the motor control panel
can be overruled by another operating-mode
command sent from a bus, for example "Start". If
the bus communication is interrupted, the motor
resumes its previous operating mode, for
example "Stop", selected with R100, Grundfos
GO or on the motor control panel.
Priority
Start/stop
button
R100, Grundfos GO or
control panel on motor
Digital input
Bus communication
1
Stop
2
Stop*
3
Manual
4
Maximum speed*
5
Stop
6
Stop
7
Maximum speed
8
Minimum speed
9
Start
10
Maximum speed
11
Minimum speed
12
Minimum speed
13
Start
14
Start