page 16
Action
BACnet
Modbus
Persistent setting?
Object for
setting
Object for
status
Register for
setting
Register for
status
Set start
BO,1 = 1
BI,2
00101.1 = 1
00201.3
No
Set stop
BO,1 = 0
BI,2
00101.1 = 0
00201.3
No
Set frost risk/
Frost risk detected
BO,4 = 1
BI,7
00101.7
00204.4
No
Set setpoint from
fieldbus
AO,0
AI,0
00102
00311
No
Temperature
control enabled
BI,1
00201.4
T
A
, air temp.
AI,27
00316
T
S
, supply temp.
AI,17
00314
T
F
, flow temp.
AI,16
00313
T
R
, return temp
AI,21
00322
Valve opening
AI,19
00319
Table 5: Data points associated with the signal diagram in Figure 12 and Figure 13.
4.3.3.2
AHU control functions when MIXIT is configured with the heating coil application
Controlled by AHU controller:
-
Outer room temperature control loop
-
Air inlet temperature control loops via heat recovery
-
Setpoint for air inlet temperature control with coil
-
Coordinating balance between heat regeneration and heat injection with mixing loop
-
Defrosting of heat recovery system
Controlled by MIXIT:
-
Direct control of the air temperature at the coils according to setpoint from AHU controller.
-
Safety functions:
o
Heating coil preheat
o
Heating coil frost protection (may be activated from AHU controller)
o
Valve anti stick functionality
4.4
Integration of MIXIT in AHU control with MIXIT configured for the radiator heating
application
It is a prerequisite that MIXIT is configured for the radiator heating application to follow the below guide.
When configured by the radiator application the PREHEAT and FROST states are not part of the state
machine, e.g. compare Figure 14 and Figure 7. It is up to the integrator to program these features if
required.