A.1.4. Electrical connection
Conductors
See
.
Torques
See
.
Line reactors
The maximum line reactor size in front of the drive must not exceed the following values:
P2
[kW]
Maximum line reactor
[mH]
1450-2000 rpm
1450-2200 rpm
2900-4000 rpm
4000-5900 rpm
0.25 - 3
1.5
1.5
4
0.7
0.7
5.5
0.9
0.3
7.5
0.6
0.6
11
0.3
0.3
Exceeding these values creates resonance between the reactor and the drive, which reduces the life of the product.
Short-circuit current
If a short circuit occurs, the pump can be used on a mains supply delivering not more than 5000 RMS symmetrical amperes, 600 V maximum.
Fuses
Fuses used for motor protection must be rated for minimum 500 V. Motors up to and including 10 hp require class K5 UL-listed fuses. Any UL-
listed fuse can be used for motors of 15 hp.
Branch-circuit protection
When the pump is protected by a circuit breaker, the circuit breaker must be rated for a maximum voltage of 480 V. The circuit breaker must be
of the "inverse time" type.
Overload protection
Degree of overload protection provided internally by the drive, in percent of full-load current: 102 %.