DANGER
Electric shock
Death or serious person-
al injury
‐
Make sure there are
at least 3 m free ca-
ble above the maxi-
mum liquid level.
DANGER
Crushing hazard
Death or serious person-
al injury
‐
Make sure that the
lifting bracket is tight-
ened before lifting
the pump.
Mechanical installation
When mounted on a base stand or brackets, the
pump must be installed outside the pit. An inlet line
must be connected to the pump.
A dimensional sketch for each installation type can be
found at the end of this booklet.
Before installing the
product, make sure that
the bottom of the pit is
even.
WARNING
Electric shock
Death or serious person-
al injury
‐
It must be possible to
switch off the power
supply and lock the
main switch in posi-
tion 0 to ensure that
the power supply
cannot be switched
on unintentionally.
‐
Any external voltage
connection to the
pump must be
switched off before
working on the
pump.
The pump must not run
dry. Dry running can
cause ignition hazard.
Install an independent
secondary level switch
to ensure that the pump
is stopped in case the
primary stop level switch
is not working.
14