4
CONTENTS
Page
1.
General description
4
2.
Applications
4
2.1
Pumped liquids
4
3.
Installation
5
3.1
Terminal box positions
5
3.2
Changing the terminal box position
5
3.3
Changing the nameplate position
5
3.4
Non-return valve
5
3.5
Insulation
5
3.6
Frost protection
5
4.
Electrical connection
6
4.1
Supply voltage
6
4.2
Wiring diagram
7
5.
Start-up
8
6.
Functions
8
6.1
Control modes
8
6.2
Selection of control mode
8
6.3
Max. or min. curve duty
10
6.4
Constant curve duty
10
6.5
Temperature influence
10
6.6
Indicator lights
11
6.7
External fault indication
11
6.8
External analog 0-10 V controller
12
6.9
External forced control
12
6.10 Deactivating the control panel
12
6.11 Bus communication
12
6.12 Wireless remote control
13
7.
Setting the pump
13
7.1
Factory settings
13
7.2
Control panel
13
7.3
R100
16
7.4
Menu OPERATION
17
7.5
Menu STATUS
17
7.6
Menu INSTALLATION
18
7.7
Priority of settings
19
8.
Fault finding chart
20
9.
Megging
21
9.1
High-voltage test
21
10.
Technical data
21
11.
Disposal
22
Before beginning installation procedures,
these installation and operating instruc-
tions should be studied carefully. The in-
stallation and operation should also be in
accordance with local regulations and ac-
cepted codes of good practice.
1. General description
The UPE Series 2000 is a complete range of circula-
tor pumps with integrated differential pressure con-
trol enabling adjustment of pump performance to the
actual system requirements. In many systems, this
will mean a considerable reduction in power con-
sumption, prevent noise from thermostatic valves
and similar fittings, and improve the control of the
system.
The desired head can be set on the pump control
panel.
These instructions apply to the pump types UPE
50-120, UPE 65-120, UPE 80-120 and UPE 100-60.
The pump offers the following functions:
•
Proportional-pressure control
(factory setting).
The head is changed in accordance with the flow
demand. The desired head can be set on the
pump control panel.
•
Constant-pressure control
. A constant head is
maintained, irrespective of flow demand. The de-
sired head can be set on the pump control panel.
•
Constant curve duty
.
The pump runs at a con-
stant speed on or between the max. and min.
curves.
•
Temperature influence
. The head varies depend-
ing on the liquid temperature.
•
External fault signal
via a potential-free output.
•
External analog control
of head or speed from
an external 0-10 V signal transmitter.
•
External forced control
via inputs for:
- Start/stop,
- Max. curve,
- Min. curve (night-time duty).
•
Bus communication
. As the UPE Series 2000 in-
corporates an input for bus communication, the
pump can be controlled and monitored by a
GRUNDFOS Pump Management System 2000 or
a building management system.
•
Remote control
. The pump can be operated by
means of the GRUNDFOS wireless remote control
R100.
2. Applications
The UPE Series 2000 is designed for circulating liq-
uids in heating systems. The pumps can also be
used in domestic hot-water systems.
UPE Series 2000 is suitable for:
• systems with a
constant flow
where it is desirable
to optimize the setting of the pump duty point and
• systems with
variable flow-pipe temperatures
.
2.1 Pumped liquids
Thin, clean, non-aggressive and non-explosive liq-
uids, not containing solid particles, fibres or mineral
oil.
In
heating systems
,
the water should meet the re-
quirements of accepted standards on water quality in
heating systems, e.g. the German standard VDI
2035.
In
domestic hot-water systems
, it is advisable to
use UPE pumps only for water with a degree of hard-
ness lower than approx. 14°dH.
For water with a higher degree of hardness a direct-
coupled TPE pump is recommended.
The pump must not be used for the trans-
fer of inflammable liquids such as diesel
oil, petrol or similar liquids.