1.3.2 –  HORIZONTAL PARTITION 

 

Minimum  thickness  of  concrete  ceilings  horizontal  partition  is  150  mm.  It  is  compulsory  to  use  UM  installation 

brackets. Installation brackets are delivered flat and have to be bended before installation of the product.  

 

 

 

 

 

                              

 

 

 

 

1.4 –   CONNECTION TO VENTILATION DUCT 

 

During  the  installation,  the  damper casing  cannot be  damaged,  in  particular,  can  not  take  place  deformation  or 

ovalisation. When the damper is connected to the ventilation duct, it is necessary to carry out a test of closing and 

opening. 

 

NOTE: 

Connection of the damper to ventilation or air-conditioning duct has to be done coaxially in order to avoid 

knocking  the  damper  blade  against  the  duct’s  walls  during  rotation.  This  is  the  necessary  condition  for  the 

appropriate  working  of  the  damper.    The  damper  should  be  installed  firmly.  Mechanical  tightening  and  free 

vibrations of ventilation system cannot be transferred onto the damper casing. 

 

 

1.5 –   ELECTRICAL CONNECTION 

 

Connect power supply cable and microswitches cables according to the table and electrical wiring diagram. Perform 

the test of power connections. 

 

Label indictaing the border 

line of damper installation 

 

Masonry mortar 

 

Installation bracekts 

Label indictaing the border 

line of damper installation 

Masonry mortar 

Installation bracekts 

Summary of Contents for CX-5C

Page 1: ...g should be made of masonry mortar or non shrink grout NOTE While installing damper it is inadmissible to grime a control mechanism of the damper with mortar glue or paints The control mechanism of the damper has to be absolutely protected until the masonry and painting works are completed The damper blade has to remain closed during installation and until mortar is hardened The damper casing cann...

Page 2: ... duct it is necessary to carry out a test of closing and opening NOTE Connection of the damper to ventilation or air conditioning duct has to be done coaxially in order to avoid knocking the damper blade against the duct s walls during rotation This is the necessary condition for the appropriate working of the damper The damper should be installed firmly Mechanical tightening and free vibrations o...

Page 3: ...zki POLAND tel 48 91 432 35 20 fax 48 91 432 35 36 e mail info gryfit com www gryfit com 1 5 1 CX 5C SMOKE CONTROL DAMPER with electromagnet and FDG 8 actuator 1 5 2 CX 5C SMOKE CONTROL DAMPER with electromagnet FDG 8 actuator and EMS 1 5 3 CX 5C SMOKE CONTROL DAMPER with SDG actuator ...

Page 4: ...er will close in less then 71s Once it is closed remove the voltage supply from the actuator To open smoke control damper CX 5C apply impulse to the electromagnet recommended from 1s up to 3s which will trigger the mechanism and close the damper within not longer than 30s Once the mechanism was triggered it is necessary to fully close the damper in order to re arm the mechanism ACTUATOR CHARACTERI...

Page 5: ...stributor 4 STORAGE The damper is delivered in the closed position with the complete control mechanism installed and blocked by the mechanical lock in case of FDG actuator that has to be removed before commissioning While installing the damper on the building site the industrial safety regulations should be respected and this manual should be followed in order to avoid damage of the damper The dam...

Page 6: ...cked and necessary maintenance was carried out by personnel authorized by the Manufacturer at least once in the year and it is documented by the written report delivered to Manufacturer or its local Distributor without delay after product check If this condition was not met a guarantee period would be limited to one year Distributor is allowed to extend guarantee conditions to its own risk Warrant...