2.1.2 –   CX-5C WITH SDG ACTUATOR OR WITH OPTIONAL EMS MODULE 

 

To close smoke control damper CX-5C apply voltage at actuator wires marked as 1 and 2. The damper will close 

after less then 30s. To open smoke control damper CX-5C apply voltage at actuator wires marked as 1 and 3. The 

damper will open after less then 30s. 

 

NOTE

:

  

-

  If the damper has been exposed to fire, it should be replaced with a new one. 

 

-

  While returning the damper to the closed position, it is recommended to switch off the smoke extraction system 

fans. 

 

 

3 –  

MAINTENANCE AND SERVICE 

 

The damper does not required special maintenance. However, it is advisable to control the proper working of the 

damper  and  make  a  written  report  once  a  year.  Maintenance  and  service  should  be  carried  out  by  authorized 

personnel who have been trained in maintenance by Manufacturer or its local Distributor.  

 

 

4 –  

STORAGE 

 

The damper is delivered in the closed position, with the complete control mechanism installed and blocked by the 

mechanical  lock  (in  case  of  FDG  actuator)  that  has  to  be  removed  before  commissioning.  While  installing  the 

damper  on  the  building  site,  the  industrial  safety  regulations  should  be  respected  and  this  manual  should  be 

followed in order to avoid damage of the damper. 

The dampers should be protected from moisture and mechanical shock or impact. It is forbidden to store more than 

two dampers one on top of the other. In case of storage on the ground, the dampers should be put on protective 

pads in order to avoid damage or deformation of the casing. 

 

During the transport, the damper should be always in the closed postion and in case of FDG actuator it should be 

blocked. To do it, use the hex key in slot (1) and rotate it in the direction indicated by the arrow below the slot until 

display under the main indicator (3) of the actuator reaches 90 degrees position i.e. damper in closed position. To 

block the actuator in this position, turn the screw (2) using screwdriver in the direction indicated by the arrow below. 

Now you can release the hex key. 

 

 

Label of the FDG-8-230 actuator.  

 

3

 

 

2

 

 

                1

 

 

Summary of Contents for CX-5C

Page 1: ...g should be made of masonry mortar or non shrink grout NOTE While installing damper it is inadmissible to grime a control mechanism of the damper with mortar glue or paints The control mechanism of the damper has to be absolutely protected until the masonry and painting works are completed The damper blade has to remain closed during installation and until mortar is hardened The damper casing cann...

Page 2: ... duct it is necessary to carry out a test of closing and opening NOTE Connection of the damper to ventilation or air conditioning duct has to be done coaxially in order to avoid knocking the damper blade against the duct s walls during rotation This is the necessary condition for the appropriate working of the damper The damper should be installed firmly Mechanical tightening and free vibrations o...

Page 3: ...zki POLAND tel 48 91 432 35 20 fax 48 91 432 35 36 e mail info gryfit com www gryfit com 1 5 1 CX 5C SMOKE CONTROL DAMPER with electromagnet and FDG 8 actuator 1 5 2 CX 5C SMOKE CONTROL DAMPER with electromagnet FDG 8 actuator and EMS 1 5 3 CX 5C SMOKE CONTROL DAMPER with SDG actuator ...

Page 4: ...er will close in less then 71s Once it is closed remove the voltage supply from the actuator To open smoke control damper CX 5C apply impulse to the electromagnet recommended from 1s up to 3s which will trigger the mechanism and close the damper within not longer than 30s Once the mechanism was triggered it is necessary to fully close the damper in order to re arm the mechanism ACTUATOR CHARACTERI...

Page 5: ...stributor 4 STORAGE The damper is delivered in the closed position with the complete control mechanism installed and blocked by the mechanical lock in case of FDG actuator that has to be removed before commissioning While installing the damper on the building site the industrial safety regulations should be respected and this manual should be followed in order to avoid damage of the damper The dam...

Page 6: ...cked and necessary maintenance was carried out by personnel authorized by the Manufacturer at least once in the year and it is documented by the written report delivered to Manufacturer or its local Distributor without delay after product check If this condition was not met a guarantee period would be limited to one year Distributor is allowed to extend guarantee conditions to its own risk Warrant...

Reviews: