130
Loop 2 Setpoint Ramp Rate
Setpoint Ramp Rate For Loop 2
Dec
4201
20585
41170
RW
0 to 10000 display units per hour
(1 to 9999 is ramp rate per hour, either 0 or >10000 = Off)
Hex
1069
5069
A0D2
Loop 2 Target Setpoint
Actual Setpoint Value of Selected Loop 2 Setpoint
Dec
4203
20587
41174
RO
The Loop 1 target setpoint value when ramping.
Hex
106B
506B
A0D6
Operator Access Setpoint Ramp Rate
Value
Operator Access to Loop 2 Setpoint Ramp Rate
Dec
4204
20588
41176
RW
0
No
Hex
106C
506C
A0D8
1
Yes
Operator Access to Setpoint Edit
Value
Operator Access to Edit Loop 2 Setpoint
Dec
4206
20590
41180
RW
0
No
Hex
106E
506E
A0DC
1
Yes
Loop 2 Selected Setpoint
Value
Selected Setpoint For Loop 2
Dec
4205
20589
41178
RO
0
Main Setpoint
Hex
101F
501F
A03E
1
Alternate Setpoint
Loop 2 Actual Setpoint
Effective Setpoint Value of Selected Loop 2 Setpoint
Dec
8269
24653
49306
RO
The effective setpoint for loop 2
(current instantaneous value of the active setpoint source)
Hex
204D
604D
C09A
Aux A Input Parameters
Parameter Name & Register Address
Integer Int +1
Float
Access
Values
& Description
Auxiliary Input A Scale Minimum
Minimum Input Scaling Value
Dec
2111
18495
36990
RW
Scale value (between ±0.001 & ±10000) when input A is at
minimum value. When used for RSP, setpoint is still
constrained by setpoint limits.
Hex
083F
483F
907E
Auxiliary Input A Scale Maximum
Maximum Input Scaling Value
Dec
2112
18496
36992
RW
Scale value (between ±0.001 & ±10000) when input A is at
maximum value. When used for RSP, setpoint is still
constrained by setpoint limits
Hex
0840
4840
9080
Auxiliary Input A Offset
Offset Applied to Scaled Aux A Value
Dec
2113
18497
36994
RW
Changes effective setpoint (for multi-zone slaves. +ve values add-
ed -ve values subtracted). From +/-0.001 to 20000 units or OFF
Hex
0841
4841
9082
Auxiliary Input A Value
Auxiliary Input A Measured Value
Dec
2114
18498
36996
RO
The current input A value (scaled).
Hex
0842
4842
9084