151
Alarm 7 Value
Value at which Alarm 7 Activates
Dec
6241
22625
45250
RW
Limited by input scaling for alarm types 1 to 4
Not used for alarms 5, 6 or 7. 0 to 100% for alarms 10 to 12.
Hex
1861
5861
B0C2
Alarm 7 Rate of Change Value
Process Variable Rate of Change Alarm Threshold
Dec
6246
22630
45260
RW
Value for Rate of Change Alarm. Alarm 7 activates when PV
change exceeds this level. From 0.0 to 99999
Hex
1866
5866
B0CC
Alarm 7 Hysteresis
Alarm 7 Hysteresis Value
Dec
6242
22626
45252
RW
Deadband value (on “safe” side of alarm), through which signal must
pass before Alarm 7 deactivates. Limited by the input scaling span
Hex
1862
5862
B0C4
Alarm 7 Inhibit Enable/Disable
Value
Alarm 7 Power-up/Setpoint Change Inhibit
Dec
6243
22627
45254
RW
0
Disabled
Hex
1863
5863
B0C6
1
Enabled
Alarm 7 Status
Value
Alarm 7 Status
Dec
6244
22628
45256
RO
0
Inactive
Hex
1864
5864
B0C8
1
Active
Alarm 7 Inhibit Status
Value
Alarm 7 Inhibit Status
Dec
6245
22629
45258
RO
0
Not Inhibited
Hex
1865
5865
B0CA
1
Inhibited
Alarm 7 Label
Main Language Name For Alarm 7 In Status Screen
Dec
6247
22631
45262
RW
8 ASCII characters replacing the title “Alarm 7” in alarm status
screens when main display language is used, read/written with
Modbus functions 16 or 23. Valid characters are
0 to 9, a to z, A
to Z, plus ß ö ( ) - and _.
Hex
1867
5867
B0CE
Alarm 7 Alternate Label
Alternate Language Name For Alarm 7 In Status Screen
Dec
6248
22632
45264
RW
8 ASCII characters replacing the title “Alarm 7” in alarm status
screens when the alternate language is used, read/written with
Modbus functions 16 or 23. Valid characters are
0 to 9, a to z, A
to Z, plus ß ö ( ) - and _.
Hex
1868
5868
B0D0
Alarm 7 Minimum Duration
Alarm 7 Minimum Duration
Dec
6249
22633
45266
RW
Minimum time alarm 7 must be passed its threshold before activating
(deactivation is not affected by this parameter). From 0 to 9999 secs
Hex
1869
5869
B0D2
Recorder & Clock Parameters
Parameter Name & Register Address
Integer Int +1
Float
Access
Values
& Description
Redcording Sample Interval
Value
Recording Sample Interval
Dec
7750
23934
47868
RW
0
Every Second
Hex
1D7E
5D7E
BAFC
1
Every 2 Seconds
2
Every 5 Seconds
3
Every 10 Seconds
4
Every 15 Seconds
5
Every 30 Seconds
6
Every Minute
7
Every 2 Minutes
Summary of Contents for Chromalox 4081