GSM SMS Alarm Messenger
Pro X (Premium)
30
COMMAND (Analog to Digital Channel)
11.23)
AD Parameters Setup
PWD:XXXX,ADVALE
1
:XXXXX,NNNNN,Y,ZZZZZ,WWWWW%
1
Channel
1
XXXXX
Measuring
Range
NNNNN Start
Value
Y
1: Triggered Alarm enabled
0: Triggered Alarm disabled
ZZZZZ
Threshold High Value Setup
WWWWW
Threshold Low Value Setup
Operation:
a)
When the captured analog value is higher or lower than the threshold values,
alarm is triggered within 0.5 second.
b)
SMS, Relay On/Off, Dial Phone etc corresponding actions described on next page
will be taken.
c)
Alarm will only be re-triggered when the captured analog value returns to normal
range and then reaches beyond the threshold values again.