GSM SMS Alarm Messenger
Pro X (Premium)
34
Built-in Temperature Sensor Operation
[Pro-S]
y
Temperature Sensor [LM35DZ] is built-in with measuring range 0 ~ 100
°
C.
y
AD Channel 2 is used for temperature measuring [Pro-S, Pro-SH]
y
AD Channel 1 is available [Pro-S only]
y
AD Channel 1 is used for humidity measuring [Pro-SH only]
y
Since this is the internal built-in sensor, the response time will be relatively slow
for application of gradual temperature change.
11.26)
Manual Temperature Check
Command: PWD:
XXXX
,STATUS%
[SMS Message received]
ST:XXX;T:2005/01/28/13:00;V:XXXX;AI1:0000;AI2:0000;K1:X;K2:X;K3:X:K4:X;K5:X;
K6:X;K7:X:K8:X;OUT1:Y:OUT2:Y;OUT3:Y;#.
AI2 Current
Temperature
11.27)
Temperature Alarm Setup
PWD:XXXX,ADVALE
2
:XXXXX,NNNNN,Y,ZZZZZ,WWWWW%
2
AD
Channel
2
XXXXX
Measuring
Range
250.0 Default
NNNNN Start
Value
000.0 Default
Y
1: Triggered Alarm enabled
0: Triggered Alarm disabled
ZZZZZ
Threshold High Temperature Setup
WWWWW
Threshold Low Temperature Setup
Example:
When temperature is above 70
°
or below 15
°
, SMS alarm message will be sent to phone
number 3 and relay output 1 will be triggered.
AD
Channel
2
Measuring
Range
250.0
Start
Value
000.0
Triggered Alarm enabled
1
Threshold High Temperature Setup
070.0
Threshold Low Temperature Setup
015.0
PWD:1234,ADVALE2:250.0,000.0,1,070.0,015.0%
PWD:1234,ADCOUT2:00,0010,100%