- 11 -
STC 4-16 CT CI
3
a
ssembly
3.1 i
nstalling
the
deviCe
– The device must not be operated lying down, since the function of the heat
sink will be severely restricted.
Only with vertically arranged cooling fins
sufficient cooling is ensured.
– The device should only be installed in a room where the permissible ambi-
ent temperature range (0 °C … +50 °C ) can be maintained, even during
fluctuations in climatic conditions.
– Mount the device on a non-combustible base.
– Use mounting material suitable for the
wall properties
.
– Position the device with a minimum distance on the left and right side of
10 cm, below and above 50 cm.
• Attach four mounting screws at the installation site. The drilling distances
are shown in the drawing below.
STC 4-16 CT CI
318 mm
222 mm
#
#
Ø
6 mm
Ø1
2 mm
• Hang the unit with the mounting supports
13
on the 4 screws.
• Tighten the screws.