30309580

           

                                                                                                       

       

        Issue 1.08

 

                                       

Features 

 

Address can be set in field. 

 

Fault self-diagnostic. 

 

Reed switch testing.   

 

Built-in MCU can store 14 history messages. . 

 

Remote indicator output available.   

 

Polling LED can be set to close. 

 

2  levels  smoke  sensitivities  programmable,  complies  with 

UL268. Heat part complies with UL521. 

Description 

DI-M9101  Intelligent  Combination  Heat  Photoelectric  Smoke 
Detector  integrates  photoelectric  detection  and  fixed  temperature 
detection 

technology 

by 

combining 

smoke 

sensor 

and 

semi-conductor  heat  sensor  in  mechanism  and  circuitry  structure. 
Just  because  of  the  combination  of  smoke  detection  and  heat 
detection,  it  not  only  overcomes  the  disadvantage  that  detectors 
using  common  infrared  scattering  technology  are  insensitive  to 
black  smoke  with  small  particles,  but  also  can  pick  up  fire  with 
obvious  rise  of  temperature  such  as  alcohol  flame,  thus  extending 
its application range. 

Connection and Cabling 

Fig. 1 shows the detector bottom and Fig. 2 DB-M01 base. 

5

45

75

Cable Entry

Mounting
Hole

 

Fig. 1                              Fig. 2 

Please install the base according to following steps: 
1) 

Locate  mounting  holes  on  the  rubber  layer  of  the  base 
according to the holes on the back box, and punch the holes 
with a screwdriver. 

2) 

Count  the  number  of  cables  needed  and  punch  correct 
quantity  of  holes  with  a  screwdriver  on  the  rubber  layer. 
Thread the cables through the cable entry holes.   

3) 

Install the base onto the back box with screws. 

Warning: Do not punch mounting holes and cable entry holes 
bigger than needed. Do not punch more holes than needed.

 

There are four terminals with numbers on the base.   

1&3: Loop connection (polarity-insensitive) 
2: Positive terminal of remote indicator 
4: Negative terminal of remote indicator 
The system connection is shown in Fig. 3. 

Remote Indicator

-

+

L

O

O

P

 

O

U

T

Addressable Detector

Remote Indicator

Addressable Detector

+

-

L

O

O

P

 

I

N

 

Fig. 3 

Recommended Cabling 

1.0mm

2

 or above fire cable is recommended, laid through metal or 

flame-retardant  conduit,  but  subject  to  local  codes.  Different  color 
cables for remote indicator are used to avoid wiring mistake. 

It can connect with UL certificated intelligent control panel from our 

company.   

 

 

 

Installation 

Refer  to 

D  Series  Detector  Application  Bulletin 

for  additional 

installation instructions. 
A fixed installation direction is ensured by the location elements on 
the  detector  and  the  base.  Fix  the  base  with  two  tapping  screws, 
and then align mark A on the detector with B on the base, rotate the 
detector to align mark A with mark C (Refer to Fig. 1 and 2 for the 
position of the marks), the detector will be fitted to the base. 
Fig. 4 shows the installation of the detector. 

54.5mm

Electrical Box

Conduit

Base

Detector

 

 

Fig. 4 

Application 

Fixed  temperature  and  level  2  are  default.  The  detector  can  be 
addressed, read or written in field by using P-9910B programmer. 
In  power-on  state,  input  unlocking  password  and  press 

Clear

  to 

unlock. Press 

Function

, then press “3”, the screen shows “_” at the 

last digit.   
Input corresponding sensitivity or parameter and press 

Program

, the 

screen will show a “P”, the corresponding sensitivity or parameter is 
programmed.  Press 

Clear

  to  clear  the  "P".  Input  locking  password 

and press 

Clear

 to return. 

Parameters set using programmer 

Input Parameter 

of a Detector 

Smoke 

Sensitivity 

Heat Part 

Polling LED 

Fixed 

Normal 

Fixed 

Normal 

129 

Fixed 

OFF 

130 

Fixed 

OFF 

Read Sensitivity Level: in power-on state, pressing 

Test,

the screen 

displays  address  of  the  detector.  Pressing 

Up”,

  display  sensitivity 

level, device type and initial sensitivity in turns.   

Testing 

Before  testing,  please  ensure  that  the  detector  has  been 
installed  correctly  and  powered  up.  After  10  seconds,  testing 
begins. 

Before testing, notify the proper authorities that the system is under 
maintenance  and  will  temporarily  be  out  of  service.  Disable  the 
automatic  controls  relating  to  the  zone  or  system  under 
maintenance to avoid unwanted actions. 
All  detectors  must  be  tested  after  installation  and  periodically 
thereafter.  Testing  methods  must  satisfy  the  Authority  Having 
Jurisdiction  (AHJ).  Detectors  offer  maximum  performance  when 
tested  and  maintained  in  compliance  with  NFPA  72.  The  detector 
can be tested in the following way: 
1)  Reed Switch Testing 
Magnetic  test  zone  is  shown  in  Fig.  5.  Put  the  magnet  of 
commission tool close to that of the detector and hold on for a few 
seconds until the detector generates alarm. 

DI-M9101 Intelligent Combination

 

 

Heat Photoelectric Smoke Detector 