Description 

I-9602LW-LPG  Addressable  Gas  Detector  (the 
detector)  detects  leakage  of  liquefied  petroleum   
gas in such areas as families, hotels, apartments 
etc. 

II    Connection and Wiring 

Terminals of the back cover are shown in Fig. 1. 

 

 

Fig. 1   

D1, D2: 24VDC power cable, non-polarized. 
Z1, Z2: Loop, non-polarized. 
V+, V-: To pipe solenoid valve. When the detector 
alarms,  3s  to  7s  later,  there  is  a  +12V  pulse 
between V+ and V-. 
K1,  K2:  Normally  open  passive  contact,  it  is 
closed when alarming.   

Note: K1, K2 can

’t be used to control 220VAC 

devices.   

Wiring: 
2.5mm

2

  or above fire-resistant copper core cable 

for D1 and D2 power line. 
1.0mm

or  above  fire-resistant  cable  signal  cable 

D1  D2

Z1  Z2

K1  K2

V-  V+

www.acornfiresecurity.com

www.acornfiresecurity.com

Summary of Contents for I-9602LW-LPG

Page 1: ...www acornfiresecurity com www acornfiresecurity com...

Page 2: ...IPTION 1 II CONNECTION AND WIRING 1 III MOUNTING 2 IV APPLICATION 4 V MAINTENANCE 5 VI CAUTIONS 6 VII SPECIFICATION 7 VIII WEEE INFORMATION 8 IX LIMITED WARRANTY 8 www acornfiresecurity com www acornf...

Page 3: ...n polarized Z1 Z2 Loop non polarized V V To pipe solenoid valve When the detector alarms 3s to 7s later there is a 12V pulse between V and V K1 K2 Normally open passive contact it is closed when alarm...

Page 4: ...ables according to terminal instructions and installation and operation manual Finally install the detector on the base Mounting is shown in Fig 2 Sensitive Position 5 8 7 6 1 4 3 2 Fig 2 When the det...

Page 5: ...detector at following locations Where directly affected by smoke or vapor from the stove Where near strong airflow such as air inlets fans doors etc Where near bathroom or places with a lot of vapor...

Page 6: ...lication 1 After wiring and checking apply power supply green LED should flash After warm up for 3 to 6 minutes the detector works normally and lights steadily 2 When the detector is in alarm state Al...

Page 7: ...rns with three sounds of the buzzer V Maintenance 1 The detector should be tested half a year at least Use a gas cigarette lighter to test the detector the distance should be longer than 10cm Press th...

Page 8: ...near smoke exhauster Keep environment around the detector clean 3 We recommend use JJ or FCR series solenoid coming with the detector If other models are to be used please consult us 4 Don t cut off...

Page 9: ...efied petroleum gas Alarm Threshold 10 LEL propane Ingress Protection Rating IP30 Ambient Temperature 10 50 Relative Humidity 95 non condensing Material and Color of the Enclosure ABS ivory Weight 180...

Page 10: ...rrants that the product will be free from defects in design materials and workmanship during the warranty period This warranty shall not apply to any product that is found to have been improperly inst...

Page 11: ...www acornfiresecurity com www acornfiresecurity com...

Reviews: