Chapter 5 List of Parameters GK600 User Manual
- 92 -
Parameter
Designation
Scope
Factory
default
Attr
d4-05 V/f FREQ value f1
d4-07~d4-03
0.00Hz
×
d4-06 V/f voltage value V1
0.0%~100.0%
0.0%
×
d4-07 V/f FREQ value f0
0.00Hz~d4-05
0.00Hz
×
d4-08 V/f voltage value V0
0.0%~100.0%
0.0%
×
d4-09 Torque boost
0.0%~30.0%
0.0%
△
d4-10 Slip compensation gain
0.0%~300.0%
100.0%
△
d4-11
Drooping FREQ of droop
control
0.00Hz~maximum frequency
0.00Hz
△
d4-12 Current limitation source
0: Disabled
1: Set by d4-13
2: Set by AI1
3: Set by AI2
4: Set by EAI
5: Set by X6/DI
1
×
d4-13
Digital setting of current
limit value
20.0%~200.0%
160.0%
×
d4-14
Flux weakening current
limit coeff
0.001~1.000
0.500
△
d4-15 Energy saving percentage 0.0%~40.0%
0.0%
△
d4-16
V/f oscillation suppression
gain 1
0~3000
38
△
d4-17
V/f oscillation suppression
gain 2
0~3000
0
△
d4-18
Voltage setting on V/f
separated pattern
0: d1-19 digital setting
1: Set by AI1
2: Set by AI2
3: Set by EAI
4: Process PID output
5: AI1 + process PID output
0
△
d4-19
Digital voltage setting on
V/f separation pattern
0.0%~100.0%
0.0%
△
d4-20
Voltage variation time on
V/f separated pattern
0.00s~600.00s
0.01s
△
Group d5 Vector Control Parameters of Motor 2
d5-00 Reserved
Reserved
Reserve ×
d5-01
ASR Hi-speed proportional
gain Kp1
0.0~20.0
2.0
△
d5-02
ASR Hi-speed integration
time Ti1
0.000s~8.000s
0.200
△
d5-03
ASR low-speed
proportional gain Kp2
0.0~20.0
2.0
△