GK600 User Manual
Chapter 6 Specification of Parameters
-
129 -
Fig. 6-5
When X6/DI pulse input is selected as auxiliary frequency command (set b0-03 to 6), the
frequency that corresponds to maximum DI input should be: (C2-25) × [(b0-08) × (b0-06)].
When PID is selected for auxiliary frequency command, the frequency that corresponds to
maximum value of PID output should be (b0-08) × (b0-06). PID output diagrammatic sketch is
as shown in Fig. 6-6.
Fig. 6-6
When b0-05 is set to 1 (relative to master frequency): When AI1, AI2, EAI, or X6/DI pulse input
is selected for auxiliary frequency command source, the frequency that corresponds to
maximum value of these sources should be: [master frequency × (b0-06)].
Example:
When selecting AI1 as auxiliary frequency command source (set b0-03 to 3) and setting AI1 to
curve 1 (Ones place of C2-00 is 0), the frequency that corresponds to maximum input of curve
1 should be: (C2-02) × [master frequency × (b0-06)].
When X6/DI pulse input is selected as auxiliary frequency command source (set b0-03 to 6),
the frequency that corresponds to maximum DI input should be: (C2-25) × [master frequency ×
(b0-06)].
When PID is selected for auxiliary frequency command, the frequency that corresponds to
maximum value of PID output should be [master frequency × (b0-06)]. PID output diagram is as
shown in Fig. 6-7.
对应设定值
AI
模拟量
曲线
1
最大输入
(
C2-01
)
曲线
1
最小输入
(
C2-03
)
曲线
1
最大输入对应
设定值(
C2-02
)
曲线
1
最小输入对应
设定值(
C2-04
)
0
PID
输出
(b0-08)×(b0-06)
频率输出
最大值
Corresponding set value
Set value that corresponds to
maximum input of curve 1
(C2-02)
Set value that corresponds to
minimum input of curve 1
(C2-04)
Minimum input of
curve 1 (C2-03)
Maximum
input of curve
1 (C2-01)
AI analog
Frequency output
PID output
Maximum value