GK600 User Manual
Chapter 6 Specification of Parameters
-
153 -
40: Length clear
Used with "length count" terminal, to clear the length calculated.
41~62: Reserved
63: Simple PLC paused
When simple PLC is running and this terminal is enabled, the current PLC status (run time
and step) will be memorized, and the drive will run at 0Hz. When this terminal is disabled,
the drive restores its running from the memorized moment.
64: Simple PLC disabled
When simple PLC is running, and this terminal is enabled. The status of PLC will be cleared
and the output frequency is 0Hz. When this terminal is disabled again, the drive resumes
PLC running from step 0.
65: Simple PLC stop memory clear
Under simple PLC running, if this terminal is enabled in stop status, the memorized
information of PLC running step, running time and running frequency will be all cleared.
Refer to parameter Group F2 for more information.
66: Start wobble frequency
This terminal takes effect only when F3-00 is set to "1: wobble frequency function enabled "
and F3-01 ones place is set to “started through terminal”. When this terminal is disabled, the
drive runs at present frequency setting. When this terminal is enabled, the drive would
activate wobble-frequency running immediately. Refer to Group F3 for details of wobble
frequency.
67: Clear wobble frequency status
When the drive is running at wobble frequency, if this terminal is enabled, the memorized
wobble frequency status will be cleared, no matter which wobble frequency start method
(automatic/ via terminal) is taken. When this terminal is disabled, wobble frequency would
resume. Refer to Group F3 for information of wobble frequency.
68: Run prohibited
When this terminal is enabled, the drive will coast to stop if it's running, and will prohibit start
running if it's in a standby state. This terminal mainly applies to the situation where safety
interlocking is required. Only after this terminal becomes disabled, the drive can be
restarted.
69: DC brake in run
When this terminal is enabled, the drive will immediately fall into DC brake. After the
terminal becomes disabled, the drive will be restored to normal state and ramp up to the
frequency setting with the set ramp up time.
ATTENTION:
When this terminal is enabled, output frequency does not need to decelerate to braking start
frequency, but will directly inject DC whose value is set by b1-15.
70~99: Reserved