GK600 User Manual
Chapter 6 Specification of Parameters
-
169 -
C2-13 Curve 3 maximum input
Range: input of curve 3
inflection point A ~110.0%
Factory default:
100.0%
C2-14
Set value corresponding to
curve 3 maximum input
Range: -100.0%~100.0%
Factory default:
100.0%
C2-15
Input of curve 3 inflection
point A
Range: input of curve 3
inflection point B ~ curve 3
maximum input
Factory default: 0.0%
C2-16
Set value corresponding to
input of curve 3 inflection
point A
Range: -100.0%~100.0%
Factory default: 0.0%
C2-17
Input of curve 3 inflection
point B
Range: curve 3 minimum
input~ input of curve 3
inflection point A
Factory default: 0.0%
C2-18
Set value corresponding to
input of curve 3 inflection
point B
Range: -100.0%~100.0%
Factory default: 0.0%
C2-19 Curve 3 minimum input
Range: -110.0%~ input of
curve 3 inflection point B
Factory default: 0.0%
C2-20
Set value corresponding to
curve 3 minimum input
Range: -100.0%~100.0%
Factory default: 0.0%
Curve 3 is defined by C2-13~C2-20. The usage of curve 3 is the same as that of curve 2.
C2-21 AI1 terminal filtering time
Range: 0.000s~10.000s
Factory default: 0.1s
C2-22 AI2 terminal filtering time
Range: 0.000s~10.000s
Factory default: 0.1s
C2-23 EAI terminal filtering time
Range: 0.000s~10.000s
Factory default: 0.1s
C2-21~C2-23 define the filtering time of analog input terminals AI1, AI2 and EAI. Long filtering
time results in strong immunity from interference but slow response, while short filtering time
brings rapid response but weak immunity from interference.
C2-24 DI maximum input
Range: C2-26~50.0kHz
Factory default:
50.0kHz
C2-25
Set value corresponding to
DI maximum input
Range: -100.0%~100.0%
Factory default:
100.0%
C2-26 DI minimum input
Range: 0.0kHz~C2-24
Factory default:
0.0kHz
C2-27
Set value corresponding to
DI minimum input
Range: -100.0%~100.0%
Factory default: 0.0%
When digital input terminal X6/DI receives pulse signal as frequency setting, the relation