GK600 User Manual
Chapter 6 Specification of Parameters
-
171 -
Output range of DO pulse frequency is 0~C3-09 (maximum output pulse frequency). The
ranges of corresponding digital output of AO1, EAO and DO are as shown in the table 6-15.
Table 6-15
Parameter value
Function
Range
0
No output
No output
1
Set FREQ
0~maximum frequency
2
Output frequency
0~maximum frequency
3
Output current
0~2 times the rated current of inverter
4
Output torque
0~2 times the rated torque
5
Output voltage
0~2 times the rated voltage of motor
6
Output power
0~ 2 times the rated power
7
Bus voltage
0~1000V
8
Reserved
Reserved
9
Torque current
0~2 times the rated current of motor
10
Magnetic flux current
0~ 2 times the rated current of motor
11
AI1
0~10V/0~20mA
12
AI2
-10V~10V
13
EAI
0~10V/0~20mA
14
Reserved
Reserved
15
DI
0~50kHz
16
Communication input
percentage
0~65535
17
Output frequency before
compensation
0~maximum frequency
18
Output current (relative to
motor rated current)
0~2 times of rated output current of the
motor
19
Output torque (direction
hinted)
-2 times rated torque~2 times rated
torque
20
Set torque (direction
hinted)
-2 times rated torque~2 times rated
torque
C3-03 AO1 offset
Range: -100.0%~100.0%
Factory default: 0.0%
C3-04 AO1 gain
Range: -2.000~2.000
Factory default: 1.000
When users need to chang AO1 measuring range or correct the meter error, it can be realized
by setting of C3-03 and C3-04. When using factory default set: 0~10V (or 0~20mA) of AO1
corresponds to “0~maximun”. See table 6-15 for details. By expressing standard output of AO1