GK600 User Manual
Chapter 6 Specification of Parameters
-
175 -
Group C4 Automatic Correction of Analog Input
Parameter Group C4 is used to perform automatic correction of analog input channels,
obtaining the gain and offset of corresponding channel automatically. They can automatically
modify the measuring range of corresponding channel or correct meter error.
C4-00
Analog correction
Range: 0~3
Factory default: 0
0: No correction
No correction to any analog input.
1: Correct AI1
Automatically correct analog AI1.
2: Correct AI2
Automatically correct analog AI2.
3: Correct EAI
Automatically correct analog EAI.
C4-01
Sampling value of AI1
calibration point 1
Range: 0.00V~10.00V
Factory default:
1.00V
C4-02
Input value of AI1
calibration point 1
Range: 0.00V~10.00V
Factory default:
1.00V
C4-03
Sampling value of AI1
calibration point 2
Range: 0.00V~10.00V
Factory default:
9.00V
C4-04
Input value of AI1
calibration point 2
Range: 0.00V~10.00V
Factory default:
9.00V
C4-05
Sampling value of AI2
calibration point 1
Range: -10.00V~10.00V
Factory default:
1.00V
C4-06
Input value of AI2
calibration point 1
Range: -10.00V~10.00V
Factory default:
1.00V
C4-07
Sampling value of AI2
calibration point 2
Range: -10.00V~10.00V
Factory default:
9.00V
C4-08
Input value of AI2
calibration point 2
Range: -10.00V~10.00V
Factory default:
9.00V
C4-09
Sampling value of EAI
calibration point 1
Range: 0.00V~10.00V
Factory default:
1.00V
C4-10
Input value of EAI
calibration point 1
Range: 0.00V~10.00V
Factory default:
1.00V
C4-11
Sampling value of EAI
calibration point 2
Range: 0.00V~10.00V
Factory default:
9.00V