Chapter 6 Specification of Parameters GK600 User Manual
- 192 -
d3-23
Overload protection mode
of motor 2
Range: 0~2
Factory default: 1
d3-24
Overload protection
detection time of motor 2 Range: 0.1min~15.0min
Factory default:
5.0min
d3-25
Input channel of motor 2
temperature transducer
signal
Range: 0~2
Factory default: 0
d3-26
Thermal protection
threshold of motor 2
temperature transducer
Range: 0.00V~10.00V
Factory default:
10.00V
Group d4 V/f Control Parameters of Motor 2
Set control parameters in Group d4 when motor 2 is selected as current loaded motor on which
V/f control is performed. The specification of V/f control parameters of motor 2 in Group d4 is
exactly the same with that of V/f control parameters of motor 1 in Group d1.
d4-00 V/f curve setting
Range: 0~8
Factory default: 0
d4-01 V/f frequency value f3
Range: 0.00Hz~rated frequency
of motor
Factory default:
50.00Hz
d4-02 V/f voltage value V3
Range: 0.0%~100.0%
Factory default:
100.0%
d4-03 V/f frequency value f2
Range: d4-05~d4-01
Factory default:
0.00Hz
d4-04 V/f voltage value V2
Range: 0.0%~100.0%
Factory default:
0.0%
d4-05 V/f frequency value f1
Range: d4-07~d4-03
Factory default:
0.00Hz
d4-06 V/f voltage value V1
Range: 0.0%~100.0%
Factory default:
0.0%
d4-07 V/f frequency value f0
Range: 0.00Hz~d4-05
Factory default:
0.00Hz
d4-08 V/f voltage value V0
Range: 0.0%~100.0%
Factory default:
0.0%
d4-09 Torque boost
Range: 0.0%~30.0%
Factory default:
0.0%
d4-10 Slip compensation gain
Range: 0.0%~400.0%
Factory default:
100.0%