GK600 User Manual Chapter 6 Specification of Parameters
-
215 -
F2-01
Setting of multi-step 0
Range: 000~327
Factory default:
000
Ones place: frequency setting
Sets the frequency of step 0 of simple PLC.
0: Multi-step frequency 0 (F1-02)
1:AI1
2:AI2
3: EAI (on IO option board)
4: X6/DI pulse input
5: Process PID output
6: Multi-step frequency
7: Communication
Tens place: run direction
Sets the run direction for step 0 of simple PLC.
0: Forward
1: Reverse
2: Determined by run command
Hundreds place: Accel/Decel time option
Sets the Accel/Decel time step 0.
0: Accel/Decel time 1
1: Accel/Decel time 2
2: Accel/Decel time 3
3: Accel/Decel time 4
The Accel/Decel time of simple PLC running is set here, not determined by digital input terminal
"Accel/Decel time determinant 1~2". In addition, Accel/Decel time unit is set through thousands
place of F2-00 and is independent of the setting of b2-00.
F2-02
Run time of step 0
Range: 0.0~6000.0s(min)
Factory default:
0.0s
Sets the run time for step 0 of simple PLC and the time unit is set by thousands place of F2-00.
F2-03
Setting of step 1
Range: 000~327
Factory default:
000
Ones place: frequency setting
0: Multi-step frequency 1 (F1-03)
1~7: same as F2-01
Tens place: run direction (same as F2-01)
Hundreds place: Accel/Decel time option (same as F2-01)