Chapter 6 Specification of Parameters
GK600 User Manual
- 220 -
F2-30
Run time of step 14
Range: 0.0~6000.0s(min)
Factory default:
0.0s
Sets the run time of step 14 of simple PLC. The time unit is set by thousands place of F2-00.
F2-31
Setting of step 15
Range: 000~327
Factory default:
000
Ones place: frequency setting
0: Multi-step frequency 15 (F1-17)
1~7: same as F2-01
Tens place: run direction (same as F2-01)
Hundreds place: Accel/Decel time option (same as F2-01)
F2-32
Run time of step 15
Range: 0.0~6000.0s(min)
Factory default:
0.0s
Sets the run time for step 15 of simple PLC. The time unit is set by thousand's place of F2-00.
ATTENTION:
Digital input terminals "simple PLC paused", "simple PLC disabled" and "simple PLC stop
memory clear" can be used during the running of simple PLC. See specification of digital
input of Group C0 for details.
Group F3 Wobble Frequency and Fixed Length Count
Wobble frequency function is usually used in textile and chemical fiber industries where
traverse motion is required. Wobble frequency control process is as follows: accelerate to the
pre-frequency of wobble frequency function according to the current Accel time. Maintain this
frequency for a period of time and run to center frequency of wobble frequency according to the
current Accel/Decel time (i.e. the set frequency set by parameter group b0). Then run in a cyclic
manner according to wobble frequency amplitude, hopping frequency, wobble frequency cycle
time, and frequency ramp up time. When a stop command is given, the drive will ramp down to
stop according to the set Decel time.