GK600 User Manual Chapter 6 Specification of Parameters
-
229 -
ATTENTION:
When this parameter value is set to 0000, run frequency (Hz) would be displayed as default.
Example:
To display run frequency, output current, motor speed and AI1 sampled value, L1-00 should be:
0000 0001 1000 1001, i.e. set L1-00 to 0189.
L1-01
Display parameter setting
2 on run status
Range: 0000~00FF
Factory default:
0000
0: No display
1: Display
Ones place
BIT0: Run linear speed (m/s)
BIT1: Set linear speed (m/s)
BIT2: Input terminal status
BIT3: Output terminal status
Tens place
BIT0: PID setting (%)
BIT1: PID feedback (%)
BIT2: Set length (m)
BIT3: Actual length (m)
Hundreds place: Reserved
Thousands place: Reserved
L1-02
Display parameter setting
on stop status
Range: 0000~FF7F
Factory default:
0003
Sets LED displayed parameters on stop status. When a number of parameters are selected,
skim-through could be realized via key >> on control panel.
0: No display
1: Display
Ones place
BIT0: Frequency setting (Hz)
BIT1: Bus voltage (V)
BIT2: Input terminal status
BIT3: Output terminal status
Tens place
BIT0: AI1 (V)
BIT1: AI2 (V)
BIT2: EAI (V)
BIT3: Reserved