Chapter 5 List of Parameters GK600 User Manual
- 80 -
Parameter
Designation
Scope
Factory
default
Attr
41~62: Reserved
63: Simple PLC paused
64: Simple PLC disabled
65: Simple PLC stop memory clear
66: Start wobble frequency
67: Clear wobble frequency status
68: Run prohibited
69: DC brake in run
70: Analog input curve switching
71~99: Reserved
C0-11
Filtering time of digital input
terminal
0.000s~1.000s
0.010s
△
C0-12 Delay time of terminal X1 0.0s~3600.0s
0.0s
△
C0-13 Delay time of terminal X2 0.0s~3600.0s
0.0s
△
C0-14
Digital input terminal
enabled status setting 1
Ones place: X1
0: Positive logic
1: Negative logic
Tens place: X2 (same as ones place)
Hundreds place: X3 (same as ones
place)
Thousands place: X4 (same as ones
place)
0000
×
C0-15
Digital input terminal
enabled status setting 2
Ones place: X5
0: Positive logic
1: Negative logic
Tens place: X6 (valid as ordinary
terminal, same as ones place)
Hundreds place: (on IO option board,
same as ones place)
Thousands place: reserved
0000
×
C0-16
Digital input terminal
enabled status setting 3
Ones place: AI1
0: Positive logic
1: Negative logic
Tens place: AI2 (same as ones place)
Hundreds place: EAI (on IO option
board, same as ones place)
Thousands place: reserved
0000
×
C0-17
Terminal UP/DOWN FREQ
adjustment action
Ones place: at stop
0: Cleared
1: Maintained
Tens place: on power loss
0: Cleared
0000
△