GK600 User Manual
Chapter 5 List of Parameters
- 83 -
Parameter
Designation
Scope
Factory
default
Attr
1: Detected speed value
Tens place: FDT2 detected object
0: Speed set value (FREQ after
Accel/Decel)
1: Detected speed value
C1-10 FDT1 upper value
0.00Hz~maximum FREQ
50.00Hz
△
C1-11 FDT1 lower value
0.00Hz~maximum FREQ
49.00Hz
△
C1-12 FDT2 upper value
0.00Hz~maximum FREQ
25.00Hz
△
C1-13 FDT2 lower value
0.00Hz~maximum FREQ
24.00Hz
△
C1-14
Detection width of FREQ
attained
0.00Hz~maximum FREQ
2.50Hz
△
C1-15
Zero current detection
value
0.0%~50.0%
5.0%
△
C1-16 Zero current detection time
0.01s~50.00s
0.50s
△
Group C2 Analog and Pulse Input
C2-00 Analog input curve
Ones place: AI1 input curve
0: Curve 1 (2 points)
1: Curve 2 (4 points)
2: Curve 3 (4 points)
3: Curve 2 and curve 3 switchover
Tens place: AI2 input curve
(same as ones place)
Hundreds place: EAI input curve
(same as ones place)
Thousands place: reserved
0210
×
C2-01 Curve 1 maximum input
Curve 1 minimum input ~ 110.0%
100.0%
△
C2-02
Corresponding set value of
curve 1 maximum input
-100.0%~100.0%
100.0%
△
C2-03 Curve 1 minimum input
-110.0% ~ curve 1 maximum input
0.0%
△
C2-04
Corresponding set value of
curve 1 minimum input
-100.0%~100.0%
0.0%
△
C2-05 Curve 2 maximum input
Range: input of curve 2 inflection
point A~110.0%
100.0%
△
C2-06
Set value corresponding to
curve 2 maximum input
Range: -100.0%~100.0%
100.0%
△
C2-07
Input of curve 2 inflection
point A
Input of curve 2 inflection point B ~
curve 2 maximum input
0.0%
△
C2-08
Set value Cor. to input of
curve 2 inflection point A
Range: -100.0%~100.0%
0.0%
△