Chapter 5 List of Parameters GK600 User Manual
- 88 -
Parameter
Designation
Scope
Factory
default
Attr
d0-23
Overload protection of
motor 1
0: No protection
1: Judged by motor current
2: Judged by temperature transducer
1
×
d0-24
Overload protection
detection time of motor 1
0.1min~15.0min
5.0min
×
d0-25
Temperature transducer
signal input of motor 1
0: AI1
1: AI2
2: EAI (on IO board)
1
×
d0-26
Thermal protection
threshold of motor 1
temperature transducer
0.00V~10.00V
10.00V
×
Group d1 V/f Control Parameters of Motor 1
d1-00 V/f curve setting
0: Linear V/f
1: Multi-stage V/f (d1-01~d1-08)
2: 1.2nd power
3: 1.4th power
4: 1.6th power
5: 1.8th power
6: 2.0nd power
7: V/f separated mode 1
8: V/f separated mode 2
0
×
d1-01 V/f FREQ value f3
0.00Hz~motor rated FREQ
50.00Hz ×
d1-02 V/f voltage value V3
0.0%~100.0%
100.0%
×
d1-03 V/f FREQ value f2
d1-05~d1-01
0.00Hz
×
d1-04 V/f voltage value V2
0.0%~100.0%
0.0%
×
d1-05 V/f FREQ value f1
d1-07~d1-03
0.00Hz
×
d1-06 V/f voltage value V1
0.0%~100.0%
0.0%
×
d1-07 V/f FREQ value f0
0.00Hz~d1-05
0.00Hz
×
d1-08 V/f voltage value V0
0.0%~100.0%
0.0%
×
d1-09 Torque boost
0.0%~30.0%
0.0%
△
d1-10 Slip compensation gain
0.0%~400.0%
100.0%
△
d1-11 Droop control
0.00Hz~maximum FREQ
0.00Hz
△
d1-12 Current limitation mode
0: Disabled
1: Set by d1-13
2: Set by AI1
3: Set by AI2
4: Set by EAI
5: Set by X6/DI
1
×
d1-13
Digital setting of current
limit value
20.0%~200.0%
160.0%
×