Chapter 9 Product Specification
MUST400_User manual_EN_REV02 User Manual
65
Chapter 9 Product Specification
This chapter provides UPS product specification
.
9.1 Applicable Standards
The UPS has been designed to conform to the following European and international standards:
Table.9- 1: Compliance with European and International Standards
Item
Normative reference
General safety requirements for UPS
used in operator access areas
EN50091-1-1/IEC62040-1-1/AS 62040-1-1
Electromagnetic compatibility (EMC)
requirements for UPS
EN50091-2/IEC62040-2/AS 62040-2(C3)
Method of specifying the performance
and test requirements of UPS
EN50091-3/IEC62040-3/AS 62040-3(VFI SS 111)
Note: The above mentioned product standards incorporate relevant compliance clauses with generic
IEC and EN standards for safety (IEC/EN/AS60950), electromagnetic emission and immunity
(IEC/EN/ AS61000 series) and construction (IEC/EN/AS60146 series and 60950).
9.2 Environmental Characteristics
Table.9- 2: Environmental Properties
Items
Unit
Requirements
Acoustic noise level at 1 meter dB
58.0
Altitude of Operation
m
≤1000m above sea level, derate power by 1% per 100m
between 1000m and 2000m
Relative Humidity
%RH
0 to 95%, non condensing
Operating Temperature
°C
0 to 40 deg , Battery life is halved for every 10°C increase
above 20°C
UPS
Storage-Transport
Temperature
°C
-20~70
Recommended
Battery
Storage Temperature
°C
0~25 (20°C for optimum battery storage)