Chapter 7 Operator Control and Display Panel
MUST400_User manual_EN_REV02 User Manual
59
Menu name
Menu item
Meaning
Control
password 1 set
User can modify control password 1
Command
Battery
maintenance test
This test will lead to the battery being partly discharged to activate
battery until battery voltage is low. Bypass must be in normal
condition, the battery capacity should be above 25%.
Battery
self-
check test
UPS transfer to battery discharge mode to test if the battery is
normal. Bypass must be in normal condition, the battery capacity
should be above 25%.
Stop testing
Manually Stop the test including maintenance test, capacity test
UPS system
information
Monitoring
software version
Monitoring software version
Rectified
software version
Rectifier software version
Inverted software
version
Inverter software version
Serial No.
The serial NO set when delivery from the factory
Rated
information
System rated information
Module model
7.4 UPS Event Log
The follow table.7-8 gives the complete list of all the UPS events displayed by history record window and
current record window.
Table.7- 8: UPS Event List
NO.
UPS events
Description
1
FaultClr
Manually clear fault
2
Log Clr
Manually clear History log
3
Load On UPS
Inverter feeds load
4
Load On Byp
Bypass feeds load
5
No Load
There is no output power for load.
6
Batt Boost
Charger is working in boost charging mode
7
Batt Float
Charger is working in float charging mode
8
Batt Discharge
Battery is discharging
9
Batt Connected
Battery is connected already
10
Batt Not Connected
Battery is not connected.
11
Maint CB Closed
Manual maintenance breaker is closed
12
Maint CB Open
Manual maintenance breaker is opened
13
EPO
Emergency Power Off
14
Inv On Less
Available power module capacity is less then the load capacity. Please
reduce the load capacity or add extra power module to make sure that
the UPS capacity is big enough.
15
Generator Input
Generator is connected and a signal is sent to the UPS.