background image

-

27

NS3000 Series User Manual    rev.01 

Chapter 3 Operations 

This chapter introduces the basic knowledge of UPS operations, including working principle, operation mode, battery 

management and protection. 

  Warning: Hazardous mains voltage and/or battery voltage present(s) behind the 

protective cover 

1

The components that can only be accessed by opening the protective cover with tools cannot be 

operated by user. 

2

Only qualified service personnel are authorized to remove such covers.

 

3.1 Introduction 

UPS provides high quality uninterruptible AC power to your critical load. The power from  UPS is free from voltage 

and frequency variations and disturbances (interruption and spike) experienced at the Mains AC input supply. 

This  is  achieved  through  high  frequency  double  conversion  power  pulse  width  modulation  (PWM)  associated  with 

full digital signal processing control (DSP), which features high reliability and convenience for use. 

3.1.1 Principle 

As shown in fig 3-1, the AC input mains source is supplied at UPS input and converted into a DC source. This DC 

source feeds the Inverter that converts the DC source into a clean and input independent AC source. The battery powers 

the  load  through  the  inverter  in  case  of  an  AC  input  mains  power  failure.  The  utility  source  can  also  power  the  load 

through the static bypass. 

When the UPS needs maintenance or repair, the load can be transferred to maintenance bypass without interruption 

and the power module and bypass module can be removed for maintenance. 

 

Fig 3-1 System principle framework 

 

 

-

28

NS3000 Series User Manual    rev.01 

3.1.2 Bypass   

. During normal system operation the load is connected to the inverter; but in the event of a UPS overload or inverter 

failure, the load is automatically transferred to the static bypass line.   

To  provide  a  clean  (no-break)  load  transfer  between  the inverter  output  and  static  bypass  line,  the  inverter  output 

and bypass supply must be fully synchronized during normal operating conditions. This is achieved through the inverter 

control electronics,  which  makes the inverter frequency  track that of the static  bypass supply,  provided  that  the  bypass 

remains within an acceptable frequency window. 

A manually controlled maintenance bypass supply is incorporated into the UPS design. It enables the critical load to 

be powered from the utility (bypass) supply while the UPS is shut down for routine maintenance. 

  Note 

When the UPS is operating in bypass mode or on maintenance bypass, the connected equipment is 

not protected from power failures or surges and sags

 

3.1.3 Battery Temperature Compensation 

The  UPS  can  connect  temperature  sensor  which  is  in  the  battery  cabinet  to  the  UPS  monitor  unit  through  battery 

temperature interface in order to reach battery management optimization. 

 

Fig 3-2 Temperature compensation diagram 

3.2 Operation Mode 

NS3000 is an on-line, double-conversion UPS that permits operation in these modes:   

l

 Normal mode 

l

 Battery mode 

l

 Auto-Restart mode 

l

 Bypass mode 

l

 Maintenance mode (manual bypass) 

l

 ECO mode   

 

 

(Settable by s.w.) 

l

 Frequency converters mode    

  ( only to request) 

l

 Parallel operation redundancy mode      (Optional) 

Summary of Contents for NS3000 10 kVA

Page 1: ...1 NS3000 Series User Manual Rev 01 UPS NS3000 10 20 30kVA USER Manual 2 NS3000 Series User Manual Rev 01...

Page 2: ...te the static switch if excessive voltage is present at the bypass input when the bypass source is deenergized If this function is not installed and enabled there must be a warning label on the extern...

Page 3: ...al rev 01 3 2 3 Auto Restart Mode 29 3 2 4 Bypass Mode 29 3 2 5 Maintenance Mode 29 3 2 6 ECO Mode 29 3 2 7 Frequency Converters Mode 29 3 2 8 Parallel connection redundancy mode 30 3 3 Battery Manage...

Page 4: ...s any mistake for accessories contact with shipper or provider 1 3 Environment Checking Before installing UPS please check these items as below 1 Is the UPS operation environment temperature above 25...

Page 5: ...sary a system of extractor fans should be installed to aid cooling air flow An air filter should be used when the UPS is to operate in a dirty environment and should be regularly cleaned to maintain a...

Page 6: ...l Against ambient corrosive gases l Against excessive humidity and heat sources l Against dust l With the current fire prevention requirements l The operating environment temperature is within 20 25...

Page 7: ...supply the installed device should l Sensitive to DC Class B or class A in the network l Insensitive to transient current pulses l Have an average sensitivity that is adjustable between 0 3A 1A 14 NS3...

Page 8: ...epartment After the equipment has been finally positioned and secured connect the power cables as described in the following procedures 1 Verify that all the external input distribution switches of th...

Page 9: ...2 5 A Pay attention all cable are marked and have different color 6 Connect the battery according fig 2 5 A don t connect A and B cable in the shelf 1 7 In shelf 1 on the left connect the cable mark...

Page 10: ...d be double insulated with a typical 0 5 to 1 5 mm 2 cross section area for a maximum connection length between 25 and 50 meters 2 6 1 Dry Contact Interface of Battery and Environmental Temperature De...

Page 11: ...Note 1 The emergency stop action within the UPS will shut down the rectifier inverter and static bypass However it does not internally disconnect the mains input and batterypower supply To disconnect...

Page 12: ...neral warning dry contact interface diagram Table 2 7 Position Name Purpose J9 1 ALARM_NC Integrated warning relay normally closed will be open during warning J9 2 ALARM_NO Integrated warning relay no...

Page 13: ...25 NS3000 Series User Manual rev 01 2 7 Installation Diagram 26 NS3000 Series User Manual rev 01 a 10KVA 30KVA terminal block NS3030 NS3010 NS3020...

Page 14: ...ss module can be removed for maintenance Fig 3 1 System principle framework 28 NS3000 Series User Manual rev 01 3 1 2 Bypass During normal system operation the load is connected to the inverter but in...

Page 15: ...e output frequency The range of output frequency is 40Hz 70Hz Under this mode static bypass is unavailable but battery can be selected according to the actual requirements of battery mode Frequency Co...

Page 16: ...4 1 Typical 1 N parallel operation system Note when the load exceeds the capacity of the single device we recommended an external manual Bypass The cables for the parallel operation provide double in...

Page 17: ...Warning Please confirm that UPS output rotating switch point to UPS with anti misoperation stop plate for rotating switch is fixed well 1 Close UPS bypass input switch and input switch in turns The LC...

Page 18: ...aution Before making this operation read messages on display to be sure that bypass supply is regular and the inverter is synchronous with it so as not to risk a short interruption in powering the loa...

Page 19: ...chapter introduces the functions and operation instructions of the parts on UPS operator control and display panel in detail and provides LCD display information including LCD display types detailed...

Page 20: ...tus indicator Steady red Failure 6 1 2 Audible Alarm buzzer There are two different types of audible alarm during UPS operation as shown in table 6 3 Table 6 3 Description of audible alarm Alarm Purpo...

Page 21: ...rface you can select each function and press ENTER press ENTER again it will display Confirm interface 6 2 5 State Display The alarm page as below press left and right arrow to select STA in homepage...

Page 22: ...inverted power supply status Bypass power supply The system is in bypass power supply status No power supply System no output Battery equalized charging Battery is in boost charging Battery float char...

Page 23: ...hows the power is normally supply by the bypass 8 Open maintenance bypass switch and close mains input switch the inverter automatically starts and UPS operates in the normal mode after 60 seconds 9 C...

Page 24: ...harge V cell 2 4V cell selectable from 2 3V cell 2 45V cell Constant current and constant voltage charge mode Battery Charging Power Max Current kW 10 UPS capacity selectable from 0 20 UPS capacity NS...

Page 25: ...eutral cable A 1 7 In Frequency2 Hz 50 60 Switch time between bypass and inverter ms Synchronized switch 1ms Bypass voltage tolerance Vac Upper limit 10 15 or 20 default 20 Lower limit 10 20 30 or 40...

Reviews: