NS3000 Series User Manual 

6.1.1 LED Indicator 

The  LEDs  shown  on  the  mini  current  path  represent  the  various  UPS  power  paths  and  show  the 

current UPS operating status. The status description of indicators is shown in table 6-2. 

Table 6-2    Status description of indicator 

Indicator 

State 

Purpose 

Steady green 

Rectifier normal

 

 

Flashing green 

Rectifier starting, mains normal 

Steady red 

Rectifier fault 

Flashing red 

Mains abnormal 

Rectifier 

indicator 

Off 

Rectifier not operating 

Steady green 

Battery charging 

Flashing green 

Battery discharging 

Steady red 

Battery abnormal (battery failure, no battery or battery reverse) or 

battery converter abnormal (failure, overcurrent or over temperature) 

, EOD 

Flashing    red 

Battery low voltage 

Battery 

indicator 

Off 

Battery and battery converter normal, battery not charging 

Steady green 

Load power supplied by bypass 

Steady red 

Bypass power abnormal or out of normal range, or static bypass 

switch fault 

Flashing    red 

Bypass voltage abnormal 

Bypass 

indicator 

Off 

Bypass normal 

Steady green 

Load power supplied by inverter 

Flashing green 

Inverter On, start, synchronization of standby (ECO mode)   

Steady red 

System power not supplied by inverter, inverter fault   

Flashing    red 

System power supplied by inverter, inverter fault   

Inverter 

indicator 

Off 

Inverter not operating

 

 

Steady green 

UPS output ON and normal 

Steady red 

UPS output overload and overtime, or output short, or output no 

power supply 

Flashing    red 

Overload output of UPS 

Load 

indicator 

Off 

No output of UPS 

Steady green 

Normal operation 

Status 

indicator 

Steady red 

Failure 

6.1.2 Audible Alarm (buzzer) 

There are two different types of audible alarm during UPS operation as shown in table 6-3. 

  Table 6-3      Description of audible alarm 

Alarm 

Purpose 

Two short alarm with one 

long alarm 

when system has general alarm (for example: AC fault), this audible 

alarm can be heard 

Continuous alarm 

When system has serious faults (for example: fuse or hardware fault), 

this audible alarm can be heard 

 

 

 

 

6.1.3 Functional Keys 

There are 4 functional keys on operator control and display panel, which are used together with LCD. 

The functions description is shown in table 6-4 

Table 6-4    Functions of functional key 

Functional    key 

Functions 

EPO switch 

To cut off the load power to shut down the rectifier, inverter, static bypass and 

battery 

HOME 

To return the main menu   

Left arrow and righ 

arrow   

Select options in the mian menu, switch over    secondary meun pages, upward 

and downward roll    the histrical log, add and subtract the intered number   

Enter key   

confirm 

6.2 LCD Display Type 

After  UPS  starting  screen  completes  self-inspection,  main  display  shown  in  fig.  6-2  appears.  The 

main panel display for 10KVA~30KVA type is provided with six main menus, turn on/off UPS, mute or not 

button. 

 

Fig. 6-2 Homepage display 

6.2.1 Default Display 

During the operation of system, if there’s no alarm in 2 min, the system will display default. After a 

short delay, the backlight of LCD display goes off; press any key to reactivate the display. Default display 

is homepage or brand display. 

6.2.2 Data Display 

The Input Data display as below (Press left and right arrow to select “I/P” , then press “ENTER”.): 

 

Fig.6-3 I/P data display for 10KVA~30KVA UPS 

In I/P data interface, you can not input or modify data, just view them. 

Summary of Contents for NS3000 10 kVA

Page 1: ...1 NS3000 Series User Manual Rev 01 UPS NS3000 10 20 30kVA USER Manual 2 NS3000 Series User Manual Rev 01...

Page 2: ...te the static switch if excessive voltage is present at the bypass input when the bypass source is deenergized If this function is not installed and enabled there must be a warning label on the extern...

Page 3: ...al rev 01 3 2 3 Auto Restart Mode 29 3 2 4 Bypass Mode 29 3 2 5 Maintenance Mode 29 3 2 6 ECO Mode 29 3 2 7 Frequency Converters Mode 29 3 2 8 Parallel connection redundancy mode 30 3 3 Battery Manage...

Page 4: ...s any mistake for accessories contact with shipper or provider 1 3 Environment Checking Before installing UPS please check these items as below 1 Is the UPS operation environment temperature above 25...

Page 5: ...sary a system of extractor fans should be installed to aid cooling air flow An air filter should be used when the UPS is to operate in a dirty environment and should be regularly cleaned to maintain a...

Page 6: ...l Against ambient corrosive gases l Against excessive humidity and heat sources l Against dust l With the current fire prevention requirements l The operating environment temperature is within 20 25...

Page 7: ...supply the installed device should l Sensitive to DC Class B or class A in the network l Insensitive to transient current pulses l Have an average sensitivity that is adjustable between 0 3A 1A 14 NS3...

Page 8: ...epartment After the equipment has been finally positioned and secured connect the power cables as described in the following procedures 1 Verify that all the external input distribution switches of th...

Page 9: ...2 5 A Pay attention all cable are marked and have different color 6 Connect the battery according fig 2 5 A don t connect A and B cable in the shelf 1 7 In shelf 1 on the left connect the cable mark...

Page 10: ...d be double insulated with a typical 0 5 to 1 5 mm 2 cross section area for a maximum connection length between 25 and 50 meters 2 6 1 Dry Contact Interface of Battery and Environmental Temperature De...

Page 11: ...Note 1 The emergency stop action within the UPS will shut down the rectifier inverter and static bypass However it does not internally disconnect the mains input and batterypower supply To disconnect...

Page 12: ...neral warning dry contact interface diagram Table 2 7 Position Name Purpose J9 1 ALARM_NC Integrated warning relay normally closed will be open during warning J9 2 ALARM_NO Integrated warning relay no...

Page 13: ...25 NS3000 Series User Manual rev 01 2 7 Installation Diagram 26 NS3000 Series User Manual rev 01 a 10KVA 30KVA terminal block NS3030 NS3010 NS3020...

Page 14: ...ss module can be removed for maintenance Fig 3 1 System principle framework 28 NS3000 Series User Manual rev 01 3 1 2 Bypass During normal system operation the load is connected to the inverter but in...

Page 15: ...e output frequency The range of output frequency is 40Hz 70Hz Under this mode static bypass is unavailable but battery can be selected according to the actual requirements of battery mode Frequency Co...

Page 16: ...4 1 Typical 1 N parallel operation system Note when the load exceeds the capacity of the single device we recommended an external manual Bypass The cables for the parallel operation provide double in...

Page 17: ...Warning Please confirm that UPS output rotating switch point to UPS with anti misoperation stop plate for rotating switch is fixed well 1 Close UPS bypass input switch and input switch in turns The LC...

Page 18: ...aution Before making this operation read messages on display to be sure that bypass supply is regular and the inverter is synchronous with it so as not to risk a short interruption in powering the loa...

Page 19: ...chapter introduces the functions and operation instructions of the parts on UPS operator control and display panel in detail and provides LCD display information including LCD display types detailed...

Page 20: ...tus indicator Steady red Failure 6 1 2 Audible Alarm buzzer There are two different types of audible alarm during UPS operation as shown in table 6 3 Table 6 3 Description of audible alarm Alarm Purpo...

Page 21: ...rface you can select each function and press ENTER press ENTER again it will display Confirm interface 6 2 5 State Display The alarm page as below press left and right arrow to select STA in homepage...

Page 22: ...inverted power supply status Bypass power supply The system is in bypass power supply status No power supply System no output Battery equalized charging Battery is in boost charging Battery float char...

Page 23: ...hows the power is normally supply by the bypass 8 Open maintenance bypass switch and close mains input switch the inverter automatically starts and UPS operates in the normal mode after 60 seconds 9 C...

Page 24: ...harge V cell 2 4V cell selectable from 2 3V cell 2 45V cell Constant current and constant voltage charge mode Battery Charging Power Max Current kW 10 UPS capacity selectable from 0 20 UPS capacity NS...

Page 25: ...eutral cable A 1 7 In Frequency2 Hz 50 60 Switch time between bypass and inverter ms Synchronized switch 1ms Bypass voltage tolerance Vac Upper limit 10 15 or 20 default 20 Lower limit 10 20 30 or 40...