background image

-5- 

CONTENTS 

Chapter 1 Quick Start .................................................................................. 8

 

1.1 Introduction ................................................................................................................................................... 8

 

1.2 Initial Checking.............................................................................................................................................. 8

 

1.3 Environment Checking ................................................................................................................................... 8

 

1.4 Installation Checking...................................................................................................................................... 8

 

Chapter 2 Installation Guidance ................................................................... 9

 

2.1 Introduction ................................................................................................................................................... 9

 

2.2.2 Battery Room ................................................................................................................................10

 

2.2.3 Storing ..........................................................................................................................................10

 

2.3 Disassembly, Initial Checking and Positioning .............................................................................................. 10

 

2.3.1 System Packing .............................................................................................................................10

 

2.3.1.1 

Remove the ups from the pallet  .................................................................................................11

 

Fig 2-1 UPS Packing Diagram ................................................................... 11

 

2.3.2 UPS Composition ..........................................................................................................................12

 

2.3.3 Operation Space ............................................................................................................................12

 

2.3.4 Front and Back Access...................................................................................................................12

 

2.3.5 Final Positioning ...........................................................................................................................12

 

2.3.6 Cable Entry ...................................................................................................................................12

 

2.4 Protective Devices........................................................................................................................................ 12

 

2.4.1.1 Rectifier and Bypass Input Supply of the UPS .............................................................................13

 

2.4.1.2    Beakfeed Protection. ................................................................................................................14

 

2.4.3 Battery ..........................................................................................................................................15

 

2.4.3 UPS Output ...................................................................................................................................15

 

2.5 Power Cables ............................................................................................................................................... 15

 

2.5.1 Maximum stable state current and configuration of minimum cable system .....................................15

 

2.5.2 Cable Connection ..........................................................................................................................16

 

2.5.3 Connection for Battery...................................................................................................................17

 

2.6 Control and Communication Cabling ............................................................................................................ 20

 

2.6.1 Dry Contact Interface of Battery and Environmental Temperature Detection (Optional)...................20

 

2.6.2 Remote EPO Input Port (Optional) .................................................................................................21

 

2.6.3 Generator Input Dry Contact (Optional) .........................................................................................22

 

2.6.4 BCB Interface (Optional) ...............................................................................................................22

 

2.6.5 Battery Warning Output Dry Contact Interface (Optional)...............................................................23

 

2.6.6 General Warning Output Dry Contact Interface (Optional)..............................................................23

 

2.6.7 Mains Failure Warning Output Dry Contact (Optional) ...................................................................24

 

2.6.8 RS232-RS485 Port and SNMP Card Port .......................................................................................24

 

2.7    Installation Diagram .................................................................................................................................. 25

 

Chapter 3 Operations ................................................................................ 27

 

3.1 Introduction ................................................................................................................................................. 27

 

3.1.1 Principle........................................................................................................................................27

 

3.1.2 Bypass ..........................................................................................................................................28

 

3.1.3 Battery Temperature Compensation ...............................................................................................28

 

3.2 Operation Mode ........................................................................................................................................... 28

 

3.2.1 Normal Mode ................................................................................................................................29

 

3.2.2 Battery Mode ................................................................................................................................29

 

-

6

NS3000 Series User Manual    rev.01 

3.2.3 Auto-Restart Mode ........................................................................................................................29

 

3.2.4 Bypass Mode.................................................................................................................................29

 

3.2.5 Maintenance Mode ........................................................................................................................29

 

3.2.6 ECO Mode ....................................................................................................................................29

 

3.2.7 Frequency Converters Mode ..........................................................................................................29

 

3.2.8 Parallel connection redundancy mode.............................................................................................30

 

3.3 Battery Management .................................................................................................................................... 30

 

3.3.1 Normal Function ...........................................................................................................................30

 

3.3.2 Advanced Functions (Battery Self-checking and Maintenance) .......................................................30

 

3.4 Battery Protection ........................................................................................................................................ 30

 

Chapter 4 Installation of Parallel Operation System .................................... 31

 

Chapter 5 Operating Procedures................................................................ 33

 

5.1 Power Switches............................................................................................................................................ 33

 

5.2 UPS Start-up ................................................................................................................................................ 33

 

5.2.1 Normal Mode Start ........................................................................................................................33

 

5.2.2 Battery Module Start 

Only Applicable for the UPS with Battery Cold Start Elements

..............35

 

5.3 Procedure for Switching between Operation Modes....................................................................................... 35

 

5.3.1 Procedure for Switching the UPS into Battery from Normal Mode ..................................................35

 

5.3.2 Procedure for Switching the UPS into Bypass from Normal Mode ..................................................35

 

5.3.3 Procedure for Switching the UPS into Normal from Bypass Mode ..................................................36

 

5.3.4 Procedure for Switching the UPS into a Maintenance Bypass from Normal Mode ...........................36

 

5.3.5 Procedure for Switching the UPS into Normal from a Maintenance Bypass Mode ...........................36

 

5.4 Procedure for Completely Powering down a UPS.......................................................................................... 36

 

5.5 EPO Procedure............................................................................................................................................. 37

 

5.6 Language Selection ...................................................................................................................................... 37

 

5.7 Control Password ......................................................................................................................................... 37

 

Chapter 6 Operator Control and Display Panel ........................................... 38

 

6.1 Introduction ................................................................................................................................................. 38

 

6.1.1 LED Indicator ...............................................................................................................................39

 

6.1.2 Audible Alarm (buzzer) .................................................................................................................39

 

6.1.3 Functional Keys ............................................................................................................................40

 

6.2 LCD Display Type ....................................................................................................................................... 40

 

6.2.1 Default Display .............................................................................................................................40

 

6.2.2 Data Display..................................................................................................................................40

 

6.2.3 Setting Display ..............................................................................................................................41

 

6.2.4 Function Display ...........................................................................................................................41

 

6.2.5 State Display .................................................................................................................................41

 

6.2.6 Confirm Display ............................................................................................................................42

 

6.2.7 History Record Display..................................................................................................................42

 

6.3 Detailed Description of Menu Items.............................................................................................................. 43

 

6.4 Alarm List ................................................................................................................................................... 44

 

Chapter 7 Maintenance.............................................................................. 45

 

7.1 Instruction of Maintenance Operation ........................................................................................................... 45

 

7.1.1 Precautions....................................................................................................................................45

 

7.1.2 Instruction to Bypass Module.........................................................................................................45

 

Chapter 8 Product Specification ................................................................. 46

 

8.1 Applicable Standards.................................................................................................................................... 46

 

Summary of Contents for NS3000 10 kVA

Page 1: ...1 NS3000 Series User Manual Rev 01 UPS NS3000 10 20 30kVA USER Manual 2 NS3000 Series User Manual Rev 01...

Page 2: ...te the static switch if excessive voltage is present at the bypass input when the bypass source is deenergized If this function is not installed and enabled there must be a warning label on the extern...

Page 3: ...al rev 01 3 2 3 Auto Restart Mode 29 3 2 4 Bypass Mode 29 3 2 5 Maintenance Mode 29 3 2 6 ECO Mode 29 3 2 7 Frequency Converters Mode 29 3 2 8 Parallel connection redundancy mode 30 3 3 Battery Manage...

Page 4: ...s any mistake for accessories contact with shipper or provider 1 3 Environment Checking Before installing UPS please check these items as below 1 Is the UPS operation environment temperature above 25...

Page 5: ...sary a system of extractor fans should be installed to aid cooling air flow An air filter should be used when the UPS is to operate in a dirty environment and should be regularly cleaned to maintain a...

Page 6: ...l Against ambient corrosive gases l Against excessive humidity and heat sources l Against dust l With the current fire prevention requirements l The operating environment temperature is within 20 25...

Page 7: ...supply the installed device should l Sensitive to DC Class B or class A in the network l Insensitive to transient current pulses l Have an average sensitivity that is adjustable between 0 3A 1A 14 NS3...

Page 8: ...epartment After the equipment has been finally positioned and secured connect the power cables as described in the following procedures 1 Verify that all the external input distribution switches of th...

Page 9: ...2 5 A Pay attention all cable are marked and have different color 6 Connect the battery according fig 2 5 A don t connect A and B cable in the shelf 1 7 In shelf 1 on the left connect the cable mark...

Page 10: ...d be double insulated with a typical 0 5 to 1 5 mm 2 cross section area for a maximum connection length between 25 and 50 meters 2 6 1 Dry Contact Interface of Battery and Environmental Temperature De...

Page 11: ...Note 1 The emergency stop action within the UPS will shut down the rectifier inverter and static bypass However it does not internally disconnect the mains input and batterypower supply To disconnect...

Page 12: ...neral warning dry contact interface diagram Table 2 7 Position Name Purpose J9 1 ALARM_NC Integrated warning relay normally closed will be open during warning J9 2 ALARM_NO Integrated warning relay no...

Page 13: ...25 NS3000 Series User Manual rev 01 2 7 Installation Diagram 26 NS3000 Series User Manual rev 01 a 10KVA 30KVA terminal block NS3030 NS3010 NS3020...

Page 14: ...ss module can be removed for maintenance Fig 3 1 System principle framework 28 NS3000 Series User Manual rev 01 3 1 2 Bypass During normal system operation the load is connected to the inverter but in...

Page 15: ...e output frequency The range of output frequency is 40Hz 70Hz Under this mode static bypass is unavailable but battery can be selected according to the actual requirements of battery mode Frequency Co...

Page 16: ...4 1 Typical 1 N parallel operation system Note when the load exceeds the capacity of the single device we recommended an external manual Bypass The cables for the parallel operation provide double in...

Page 17: ...Warning Please confirm that UPS output rotating switch point to UPS with anti misoperation stop plate for rotating switch is fixed well 1 Close UPS bypass input switch and input switch in turns The LC...

Page 18: ...aution Before making this operation read messages on display to be sure that bypass supply is regular and the inverter is synchronous with it so as not to risk a short interruption in powering the loa...

Page 19: ...chapter introduces the functions and operation instructions of the parts on UPS operator control and display panel in detail and provides LCD display information including LCD display types detailed...

Page 20: ...tus indicator Steady red Failure 6 1 2 Audible Alarm buzzer There are two different types of audible alarm during UPS operation as shown in table 6 3 Table 6 3 Description of audible alarm Alarm Purpo...

Page 21: ...rface you can select each function and press ENTER press ENTER again it will display Confirm interface 6 2 5 State Display The alarm page as below press left and right arrow to select STA in homepage...

Page 22: ...inverted power supply status Bypass power supply The system is in bypass power supply status No power supply System no output Battery equalized charging Battery is in boost charging Battery float char...

Page 23: ...hows the power is normally supply by the bypass 8 Open maintenance bypass switch and close mains input switch the inverter automatically starts and UPS operates in the normal mode after 60 seconds 9 C...

Page 24: ...harge V cell 2 4V cell selectable from 2 3V cell 2 45V cell Constant current and constant voltage charge mode Battery Charging Power Max Current kW 10 UPS capacity selectable from 0 20 UPS capacity NS...

Page 25: ...eutral cable A 1 7 In Frequency2 Hz 50 60 Switch time between bypass and inverter ms Synchronized switch 1ms Bypass voltage tolerance Vac Upper limit 10 15 or 20 default 20 Lower limit 10 20 30 or 40...

Reviews: