௰
Ѷ
34
Table7. Environment and safety
Temperature
Humidity
Altitude
Storage temperature
0
°
C-40
°
C
<95%
<1000m
0
°
C-40
°
C
Note: if the UPS is installed or used in a place where the altitude is
above than
1000m
, the output power must be derated in use, please
refer to the following:
Altitude (M)
1000 1500 2000 2500 3000 3500 4000 4500 5000
Derating
Power
100% 95%
91%
86%
82%
78%
74%
70%
67%
Output
Voltage
Regulation
Power
Factor
Frequency
tolerance
Distortion
Overload capacity
Current
crest ratio
±
1%
0.9 lag
Synchronized
50/60Hz
±
10%
in Line mode
(AC mode)
±
0.1% of
normal
frequency in
Battery mode
THD<2%
Full load
(Linear
Load)/
<5% for
reference
non-linear
load
102%-130% load
transfers to Bypass
mode after 2 minutes
>130% load transfers
to Bypass mode after
30 second and
shutdown the output
after 1 minute
3:1
maximum