89
R
EMOTE MAINTENANCE BYPASS CONNECTION
An additional maintenance bypass may be installed on a peripheral switchboard (see diagram below), for example, o allow
replacing the UPS without interrupting the power supply to the load.
Note
: The Company provides this accessory already pre-assembled in an IP65 plastic box.
It is essential to connect the "SERVICE BYPASS" terminal (see "Views of the UPS connections") to the
auxiliary contact of the SERVICE BYPASS switch. The closure of the SERVICE BYPASS switch will open
this auxiliary contact which informs the UPS that the maintenance bypass has been inserted. The absence
of this connection may interrupt the power supply to the load and damage the UPS.
-
Use cables with cross sections in compliance with the indications given in the "Cross section of the cables" paragraph.
-
In order to connect the "SERVICE BYPASS" terminal to the auxiliary contact of the remote maintenance bypass isolator, use
1mm
2
double isolation cables.
-
If the UPS is connected to an isolation transformer, check the compatibility between the
“remote maintenance bypass”
and
the neutral regime of the installation.
REMOTE MAINTENANCE BYPASS INSTALLATION DIAGRAM
Peripheral switchboard
UPS internal connections
INPUT switch: isolator compliant with the indications given in the "UPS internal protections" section
OUTPUT switch: isolator compliant with the indications given in the "UPS internal protections" section
SERVICE BYPASS switch: isolator compliant with the indications given in the "UPS internal protections" section,
equipped with a normally closed auxiliary contact
Summary of Contents for SATURN
Page 2: ......
Page 40: ...40 MENU DISPLAY ...
Page 60: ...60 ...
Page 98: ...98 MENU DISPLAY ...
Page 118: ...118 ...
Page 156: ...156 DISPLAY MENÜ ...
Page 176: ...176 ...
Page 214: ...214 MENU AFFICHEUR ...
Page 234: ...234 ...
Page 272: ...272 MENÚ PANTALLA ...
Page 292: ......
Page 293: ......
Page 294: ...0MNSATURNK30NP5LUC ...